Plan Review Notes
Plan Review Notes For Permit 17070322
Permit Number 17070322
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-14 12:35:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1 - THE DOOR SCHEDULE DOES NOT PROPERLY
 INDICATED DOOR 02.
  
 PLEASE CLARIFY OR CORRECT.
  
  
  
 2) SHEET A 1 - THE EXISITNG OR PROPOSED OCCUPANY TYPE
 IS NOT INDICATED.
  
 PLEASE INDICATE PER NFPA 101, CHAPTER 6, OCCUPNACY
 CLASSIFICATION.
  
  
  
 3) PER # 2 ABOVE, IS THIS AN EXISTING BUSINESS OR NEW
 BUSINESS? IF NEW, WAS THE PREVIOUS OCCUPANCY THE SAME?
  
 PLEASE PROVIDE AND APPLICABLE NOTE.
  
  
  
 4) NO EXIT SIGNS ARE INDICATED.
  
 PLEASE PROVIDE EXIT SIGNAGE PER THE APPLICABLE CODE
 EXIT LOCATIONS IF EXISTING OR PROPOSED.
  
  
  
 5) THERE ARE NO INDICATIONS IF THE BUILDING OR SPACE
 HAS A FIRE ALARM SYSTEM.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  