Plan Review Notes For Permit 17070322 |
Permit Number |
17070322 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-14 12:35:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) SHEET A 1 - THE DOOR SCHEDULE DOES NOT PROPERLY | | INDICATED DOOR 02. | | | | PLEASE CLARIFY OR CORRECT. | | | | | | | | 2) SHEET A 1 - THE EXISITNG OR PROPOSED OCCUPANY TYPE | | IS NOT INDICATED. | | | | PLEASE INDICATE PER NFPA 101, CHAPTER 6, OCCUPNACY | | CLASSIFICATION. | | | | | | | | 3) PER # 2 ABOVE, IS THIS AN EXISTING BUSINESS OR NEW | | BUSINESS? IF NEW, WAS THE PREVIOUS OCCUPANCY THE SAME? | | | | PLEASE PROVIDE AND APPLICABLE NOTE. | | | | | | | | 4) NO EXIT SIGNS ARE INDICATED. | | | | PLEASE PROVIDE EXIT SIGNAGE PER THE APPLICABLE CODE | | EXIT LOCATIONS IF EXISTING OR PROPOSED. | | | | | | | | 5) THERE ARE NO INDICATIONS IF THE BUILDING OR SPACE | | HAS A FIRE ALARM SYSTEM. | | | | PLEASE PROVIDE AN APPLICABLE NOTE. | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|