Plan Review Notes
Plan Review Notes For Permit 17070322
Permit Number 17070322
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-21 09:24:34CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. PROVIDE NOTE THAT ALL LOW VOLTAGE WORK WILL BE UNDER
 SEPARATE PERMIT. FBC 105.1
 3. PROVIDE PANEL SCHEDULE, SHOWING ANY NEW OR ALTERED
 CIRCUITS. NEC 215.5, 408.4
 4. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  