Plan Review Notes
Plan Review Notes For Permit 17070322
Permit Number 17070322
Review Stop B
Sequence Number 1
Notes
Date Text
2017-07-13 14:12:472014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070322
 ADD: 3703S DIXIE HWY. SUITE A
 CONT: GREY CONSTRUCTION
 TEL: 561-845-2872
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 13/ 2017
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS DESIGNED BY GRANDEURDESIGN DOES
 NOT INDICATE THEY ARE EITHER AN ARCHITECT OR ENGINEER.
 THEY MUST SIGN AND SEAL THE PLANS PER F. S. 471 AND OR
 481 OR REMOVE THIS NAME FROM THE TITLE BLOCK. THEY
 CANNOT PRACTICE ARCHITECTURE NOR ENGINEERING. THE
 CONTRACTORS CAN PRODUCE THEIR OWN PLANS. 107.3.4.3
 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION
 TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/
 PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES
 THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN
 THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS
 THE SYSTEM UNDER THAT TRADE. FOR EACH TRADE THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE
 LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY
 ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A
 BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT
 ALL THESE TRADES UNDER ONE SHEET.
 2) SHEET A1:
 2A) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 2B) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 2C) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 2D) IS THE BUILDING FIRE SPRINKLERED?
  
 2E) THE DOOR SCHEDULE INDICATES DOORS 1, 3 & 4 ARE ALL
 SWING DOORS WITH A WIDTH OF 32 INCHES (2870).
 PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B 1008.
 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES. A 3 FOOT WIDE DOOR WOULD
 BE REQUIRED FOR A 32 INCH OPENING OR OFFSET HINGES
 ALLOWING A 34 INCH DOOR TO BE USED.
  
 2F) THE DOOR SCHEDULE INDICATES DOOR # 2 TO ALSO BE A
 32 INCH DOOR. THE PLANS APPEAR TO HAVE A ACCORDION
 STYLE DOOR BEING INSTALLED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE PROPOSED FLOOR PLAN (SHEET A1) INDICATES A NEW
 DRESSING ROOM. THE FLOOR PLAN WILL NEED TO SHOW
 COMPLIANCE WITH THE 2014 ACCESSIBILITY CODE;
  
 3A) 803.1 DRESSING, FITTING, AND LOCKER ROOMS SHALL
 COMPLY WITH 803.
 ADVISORY 803.1 GENERAL. PARTITIONS AND DOORS SHOULD BE
 DESIGNED TO ENSURE PEOPLE USING ACCESSIBLE DRESSING AND
 FITTING ROOMS PRIVACY EQUIVALENT TO THAT AFFORDED OTHER
 USERS OF THE FACILITY. SECTION 903.5 REQUIRES DRESSING
 ROOM BENCH SEATS TO BE INSTALLED SO THAT THEY ARE AT
 THE SAME HEIGHT AS A TYPICAL WHEELCHAIR SEAT, 17 INCHES
 (430 MM) TO 19 INCHES (485 MM). HOWEVER, WHEELCHAIR
 SEATS CAN BE LOWER THAN DRESSING ROOM BENCHES FOR
 PEOPLE OF SHORT STATURE OR CHILDREN USING WHEELCHAIRS.
  
 3B) 803.2 TURNING SPACE. TURNING SPACE COMPLYING WITH
 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 3C) 803.3 DOOR SWING. DOORS SHALL NOT SWING INTO THE
 ROOM UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING
 WITH 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR
 SWING.
  
 3D) 803.4 BENCHES. A BENCH COMPLYING WITH 903 SHALL BE
 PROVIDED WITHIN THE ROOM.
  
 3E) 803.5 COAT HOOKS AND SHELVES. COAT HOOKS PROVIDED
 WITHIN THE ROOM SHALL BE LOCATED WITHIN ONE OF THE
 REACH RANGES SPECIFIED IN 308. SHELVES SHALL BE 40
 INCHES (1015 MM) MINIMUM AND 48 INCHES (1220 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) WITH THE DOORS 01 & 03 BEING REQUIRED TO SWING OUT
 AND NOT IN THE CORRIDOR IS ONLY 4 FEET WIDE THAT DOES
 NOT PROVIDE COMPLIANCE WITH: 2014 FBC-B 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES. DOORS IN ANY POSITION
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN
 ONE-HALF.
  
 5) THE PLANS DO NOT INDICATE IF THE FRONT ENTRY HAS A
 LEVEL ENTRY FROM THE EXTERIOR TO THE INTERIOR TENANT
 SPACE. PLEASE PROVIDE WHERE UP TO $460.00 DOLLARS ARE
 GOING TO BE SPENT ON ACCESSIBLE UPGRADES.
 2014 ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved