2017-07-18 08:51:48 | BUILDING PLAN REVIEW |
| 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17070301 |
| W. P. B. PERMIT: 15100827 |
| ADD: 111 S. SAPODILLA AVE. |
| CONT: THE WEITZ CO. |
| TEL: (561)686-5511 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: TUES. JULY 18/ 2017 |
| ACTION: DENIED |
| |
| 1) PLEASE CORRECT THE WIND DESIGN AND CALCULATIONS FOR |
| THE LOUVER GRILLES. THE CITY APPROVED SET OF PLANS |
| INDICATES ON SHEET S.002 THE WIND DESIGN VULT TO BE 170 |
| MPH. RISK CATEGORY II, EXPOSURE C. SEE THE 2014 FBC-B |
| 1609A. |
| |
| 2) THE ENGINEERING FOR THE LOUVER GRILLES HAS NOT BEEN |
| REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD IN |
| COMPLIANCE WITH 61G15-30.003 ENGINEERING DOCUMENT |
| CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |