2017-07-25 12:30:29STAND BY AND EMERGENCY POWER SHALL COME INTO COMPLIANCE
 WITH NFPA 110.
 INSTALLATION OF EMERGENCY GENERATORS, (ATS) AUTOMATIC
 TRANSFER SWITCH SHALL COME INTO COMPLIANCE WITH NFPA
 110.
 NATURE GAS PIPING AND IT APPURTENANCES? SHALL COME INTO
 COMPLIANCE WITH NFPA 54. APPLIANCES PIPING AND OTHERS
 SHALL BE PROTECTED FROM DAMAGE FROM VEHICLE TRAFFIC.
  