2017-07-14 10:09:00 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070276 |
| ADD: 205 SOUTHERN BLVD. |
| CONT: JOHN ROSSI CONSTRUCTION |
| TEL: 561-659-5505 |
| E-MAIL: JOHNROSSI:[email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JULY 14/ 2017 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE A LIFE SAFETY PLAN. 2014 FLORIDA |
| BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 5. FIRE SPRINKLERS REQUIRED? IF SO FIRE SUPPRESSION |
| SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE SPRINKLERS |
| 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| STAIRS |
| RAMPS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE TO THE PUBLIC WAY |
| EXIT AND DIRECTIONAL SIGNAGE INCLUSIVE OF BRAILLE |
| 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| SITE REQUIREMENTS |
| ACCESSIBLE ROUTE |
| VERTICAL ACCESSIBILITY |
| SIGNAGE |
| 12. SPECIAL SYSTEMS: LIFTS |
| |
| 2) THE SHEET A101 LIST THE DESCRIPTION OF WORK IN THE |
| SCOPE OF THIS PERMIT AND WORK DEPICTED ON THE PLANS AS |
| A LEVEL 3 ALTERATION. PLEASE NOTE THERE IS ADDITIONAL |
| SQUARE FEET BEING ADDED TO THE BUILDING, BY DEFINITION |
| THIS IS AN ADDITION AND TO BE REVIEWED UNDER CHAPTER 11 |
| ( ADDITIONS) OF THE EXISTING BUILDING CODE. PLEASE |
| REVIEW THE 2014 FBC-EXISTING BUILDING CODE SECTION |
| 1101.2 CREATION OR EXTENSION OF NONCONFORMITY. AN |
| ADDITION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY |
| IN THE EXISTING BUILDING TO WHICH THE ADDITION IS BEING |
| MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, |
| FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF |
| MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. THERE |
| SEEMS TO BE (2) POSSIBLY (3) |
| VIOLATIONS TO THE BUILDING CODE WITH THE EXISTING |
| DESIGN WITHOUT THE ADDITION, THE REQUEST IN COMMENT # 1 |
| WILL VERIFY IF THERE ARE CODE VIOLATIONS. |
| |
| 2A) IN THE GENERAL AREA OF THE BAR AND INTERIOR DINING |
| ROOMS THE SQUARE FOOT AREA IS APPROXIMATELY 2,368 SQ. |
| FT. / 15= 158 OCCUPANTS. UNDER THE EXISTING BUILDING |
| CODE SECTION 805.3.1.1 SINGLE-EXIT BUILDINGS. |
| ONLY ONE EXIT IS REQUIRED FROM BUILDINGS AND SPACES OF |
| THE FOLLOWING OCCUPANCIES: |
| (1.) IN GROUP A, B, E, F, M, U AND S OCCUPANCIES, A |
| SINGLE EXIT IS PERMITTED IN THE STORY AT THE LEVEL OF |
| EXIT DISCHARGE WHEN THE OCCUPANT LOAD OF THE STORY DOES |
| NOT EXCEED 50 AND THE EXIT ACCESS TRAVEL DISTANCE DOES |
| NOT EXCEED 75 FEET. IN THIS STRUCTURE THERE ARE VARIOUS |
| EXITS BUT THEY CONVERGE TO A SINGLE EXIT DISCHARGE ON |
| THE EXTERIOR OF THE BUILDING CONVERGING TO A SINGLE |
| ENTRY/ EXIT. WITH THE ADDITION AND USE OF THE NANA WALL |
| SYSTEM THESE DOORS THESE MAYBE A PROBLEM WITH EXITING |
| IF THEY ARE TO BE CONSIDERED ON AN EGRESS PATH. THE |
| OTHER ISSUE THAT NEEDS TO BE REVIEWED IS THE USE OF |
| SLIDING GLASS DOORS WITHIN THE DINING ROOM TOWARDS THE |
| EAST SIDE SEPARATING DINING ROOMS. |
| |
| 2B) THE OTHER ISSUE THE FLOOR PLANS SHOW IS TWO SETS OF |
| STAIRS BUT THERE IS NO ACCESSIBLE ENTRANCE/ EXITS SHOWN |
| ON THE PLANS. 2014 ACCESS. CODE 206.4.1 PUBLIC |
| ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 |
| THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC |
| ENTRANCES SHALL COMPLY WITH 404. FOR THE MAIN DINING |
| ROOM/ BAR AREA THERE NEEDS TO BE (2) ACCESSIBLE |
| ENTRANCES AS WELL. |
| |
| 3) THE S1 SHEET DOES NOT HAVE THE WIND DESIGN CRITERIA |
| FOR COMPONENTS AND CLADDING. 2014 FBC-B 1603.1.4 WIND |
| DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND |
| LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS |
| GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM |
| OF THE STRUCTURE: |
| |
| 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 3.2. RISK CATEGORY. |
| |
| 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. |
| |
| 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 4) THE SUBMITTED NANA WALL PRODUCT APPROVAL WILL NEED |
| TO COMPLY WITH: FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 5) THE NANA WALL PRODUCT APPROVAL NOA 15-0225.05, |
| EITHER THE CONTRACTOR OR DESIGNER OF RECORD WILL NEED |
| TO SHOW COMPLIANCE WITH IDENTIFY GLAZING. PLEASE |
| IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 |
| FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 6) THE PLANS SHEET A100 REALLY DON?T IDENTIFY IF THE |
| NEWLY CREATED A/C SPACE AND ADJACENT OUTDOOR SEATING |
| AREA ARE UNDER ROOF COVER, THERE AGAIN THERE IS (2) |
| ISSUES OF CONCERN: |
| |
| 6A) THIS OUTDOOR SEATING AREA WOULD NEED TO BE ON AN |
| ACCESSIBLE ROUTE PLEASE PROVIDE CODE COMPLIANCE OF HOW |
| THE TRANSITION FOR THE BOTTOM TRACK WILL OCCUR, OR WILL |
| THERE BE A FLUSH SADDLE SILL AS PROVIDE ON PAGE 7 OF |
| THE PRODUCT APPROVAL? ACCESS. CODE 404.2.5 THRESHOLDS. |
| THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| |
| 6B) IF THE OUTSIDE SITTING AREA IS NOT COVERED BY A |
| ROOF THEN COMPLIANCE WITH FBC-B 1710.5.1.1 MAYBE A |
| CONCERN. |
| EXTERIOR WINDOWS AND DOORS. (EXCEPTION) 2. DOOR |
| ASSEMBLIES INSTALLED WHERE THE OVERHANG (OH) RATIO IS |
| EQUAL TO OR MORE THAN 1 NEED NOT BE TESTED FOR WATER |
| INFILTRATION. THE OVERHANG RATIO SHALL BE CALCULATED BY |
| THE FOLLOWING EQUATION: |
| OH RATIO = OH LENGTH/OH HEIGHT |
| WHERE: |
| OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN |
| OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE. |
| OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM |
| THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A |
| DOOR. |
| |
| 7A) SHEET A300 SHOWS A NEW FLAT SECTION OF ROOF, PLEASE |
| COMPLY WITH1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: (D) ROOFING PRODUCTS AND ASSEMBLIES. |
| |
| 7B) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING. |
| |
| 7C) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| ON SUBSEQUENT REVIEWS. |
| |