2017-08-01 11:30:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEW SHEETS SUBMITTED FOR ELECTRICAL, E0-1 AND E2-1,
 NOT SIGNED AND SEALED. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC 107.2.1; FS 471
 2. RECEPTACLE CONTROL NOT TO CODE. OFFICES 314 AND 315
 DO NOT SHOW ANY CONTROL. BREAK AREA DOES NOT MEET
 AMOUNT OF CONTROL REQUIRED. BOTH AREAS REQUIRE A
 MINIMUM OF 50% OF THE OUTLETS CONTROLLED PER ASHRAE
 90.1:8.4.2. ADDITIONALLY, PLAN CURRENTLY SHOWS 8
 CIRCUITS BEING CONTROLLED BY A 6 POLE CONTACTOR, WHICH
 WILL OBVIOUSLY NOT WORK. PROVIDE CORRECTIONS. FBC
 C405.7.1, FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  