Plan Review Notes For Permit 17070265 |
Permit Number |
17070265 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-08-01 11:30:20 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. NEW SHEETS SUBMITTED FOR ELECTRICAL, E0-1 AND E2-1, | | NOT SIGNED AND SEALED. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. FBC 107.2.1; FS 471 | | 2. RECEPTACLE CONTROL NOT TO CODE. OFFICES 314 AND 315 | | DO NOT SHOW ANY CONTROL. BREAK AREA DOES NOT MEET | | AMOUNT OF CONTROL REQUIRED. BOTH AREAS REQUIRE A | | MINIMUM OF 50% OF THE OUTLETS CONTROLLED PER ASHRAE | | 90.1:8.4.2. ADDITIONALLY, PLAN CURRENTLY SHOWS 8 | | CIRCUITS BEING CONTROLLED BY A 6 POLE CONTACTOR, WHICH | | WILL OBVIOUSLY NOT WORK. PROVIDE CORRECTIONS. FBC | | C405.7.1, FBC 107.2.1 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|