2017-07-19 12:14:37CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE AUTOMATIC LIGHTING CONTROLS FOR ALL FIXTURES
 PER CODE. IT APPEARS THAT THE HALL IS MISSING CONTROL,
 AND THE CONTROL FOR THE MAIN WORK AREA IS NOT CLEAR.
 CLARIFY AND/OR CORRECT. FBC 107.2.1, C405.2.2
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  