Plan Review Notes For Permit 17070265 |
Permit Number |
17070265 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-19 12:14:37 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. PROVIDE AUTOMATIC LIGHTING CONTROLS FOR ALL FIXTURES | | PER CODE. IT APPEARS THAT THE HALL IS MISSING CONTROL, | | AND THE CONTROL FOR THE MAIN WORK AREA IS NOT CLEAR. | | CLARIFY AND/OR CORRECT. FBC 107.2.1, C405.2.2 | | 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2 | | AND ASHREA 90.1: 8.4.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|