2017-07-20 14:36:292014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070265
 ADD: 501 S. FLAGLER DR. SUITE : 302
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 561-308-1590
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 20/ 2017
 ACTION: DENIED
  
 1) THE SHEET 004_A.1.1.1. INDICATES A NEW ALCOVE AND
 ENTRY DOOR, THE DOOR IS IDENTIFIED AS 315. THE DOOR
 SCHEDULE FOUND ON 007_A2.0.1 INDICATES THIS DOOR IS A
 3-0X 8-0 FOOT DOOR. THE INTERIOR SIDE OF THE ALCOVE IS
 DIMENSIONED AS 4 FOOT 6 INCHES WIDE. THE PLANS WHEN
 SCALED SHOW THE 18 INCHES ON THE LATCH SIDE OF THE DOOR
 AS REQUIRED BY THE ACCESSIBILITY CODE. WHEN THE DOOR IS
 MEASURES FOR WIDTH, IT ONLY MEASURES AS A 2 FOOT 71/2
 INCH DOOR. PLEASE NOTE FOR DOORS IN A MEANS OF EGRESS
 THE DOOR WIDTH WOULD NEED TO BE A 36 INCH WIDE DOOR.
  
 PLEASE REFER TO THE 2014 FBC-B SECTION 1008.1.1 SIZE OF
 DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 ONCE THE DOOR MEETS THE EGRESS REQUIREMENTS WITH A 4
 FOOT 6 INCH ALCOVE WIDTH YOU WILL NO LONGER HAVE THE
 REQUIRED 18 INCHES MANEUVERING CLEARANCES ON THE LATCH
 SIDE OF THE DOOR. SEE 2014 ACCESSIBILITY CODE SECTION
 404.2.4 MANEUVERING CLEARANCES, TABLE 404.2.4.1 AND
 FIGURE 404.2.4.1(A). PLEASE UPDATE THE PLANS.
  
 2) THE SHEET 004_A.1.1.1. ALSO SHOWS (2) POCKET DOORS,
 DOORS ARE IDENTIFIED AS 313B & 314B. THE DOOR SCHEDULE
 FOUND ON 007_A2.0.1 INDICATES THESE DOORS HARDWARE AS
 GROUP 3, NOTES INDICATE POCKET HARDWARE? PLEASE SHOW
 COMPLIANCE WITH :
  
 2014 ACCESSIBILITY CODE 404.2.7 DOOR AND GATE HARDWARE.
 WHERE SLIDING DOORS ARE IN THE FULLY OPEN POSITION,
 OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM
 BOTH SIDES. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER
 OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH
 309.4. OPERABLE PARTS.
  
 2014 ACCESSIBILITY CODE 309.4 OPERATION. OPERABLE PARTS
 SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE
 TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE
 FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5
 POUNDS (22.2 N) MAXIMUM.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved