2017-12-28 17:46:13 | 3RD REVIEW FBC-2014 MECHANICAL |
| PERMIT #17070253 |
| 12/28/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REFER TO SECTION 607.5.4 CONCERNING THE FLEX DUCTS |
| PENETRATING THE CORRIDOR WALLS AS SHOWN ON SHEETS M.01, |
| M.02, M.03, & M.04. THE CORRIDOR WALLS HAVE BEEN |
| DESIGNATED AS SMOKE BARRIERS ON SHEETS A.02, A.03, AND |
| A.04, AND THEREFORE ONLY STEEL DUCTS WITH THICKNESSES |
| NO LESS THAN 0.019 INCH (0.48MM) ARE PERMITTED TO |
| PENETRATE THE WALLS WITHOUT SMOKE DAMPERS- SEE |
| EXCEPTION 3 AND PROVIDE EITHER SMOKE DAMPERS TO PROTECT |
| THE PENETRATIONS, OR CHANGE THE DUCTS TO STEEL. |
| |
| 2) SHEET M.01: THE AIR BALANCE CALULATION FOR THE |
| KITCHEN DOES NOT INCLUDE THE HOOD EXHAUST AND SUPPLY |
| CFMS. |
| |
| 3) SHEET M.01: THE CARRIER INFINITY MODEL NO. |
| 24ANB748A003 IS A 4-TON 17 SEER VARIABLE SPEED UNIT. IT |
| IS INCORRECTLY LISTED AS IN THE HVAC SCHEDULES AS A |
| 5-TON, A 3.75-TON, A 3.25 TON, A 4.75 TON, AND A 2.0 |
| TON UNIT. PLEASE CORRECT THE SCHEDULES AND CORRECT THE |
| ENERGYGAUGE COMPLIANCE FORM WHICH IS ALSO LISTING |
| INCORRECT DATA FOR CAPACITIES AND EFFICIENCY RATINGS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |