Plan Review Notes
Plan Review Notes For Permit 17070253
Permit Number 17070253
Review Stop M
Sequence Number 3
Notes
Date Text
2017-12-28 17:46:133RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17070253
 12/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 607.5.4 CONCERNING THE FLEX DUCTS
 PENETRATING THE CORRIDOR WALLS AS SHOWN ON SHEETS M.01,
 M.02, M.03, & M.04. THE CORRIDOR WALLS HAVE BEEN
 DESIGNATED AS SMOKE BARRIERS ON SHEETS A.02, A.03, AND
 A.04, AND THEREFORE ONLY STEEL DUCTS WITH THICKNESSES
 NO LESS THAN 0.019 INCH (0.48MM) ARE PERMITTED TO
 PENETRATE THE WALLS WITHOUT SMOKE DAMPERS- SEE
 EXCEPTION 3 AND PROVIDE EITHER SMOKE DAMPERS TO PROTECT
 THE PENETRATIONS, OR CHANGE THE DUCTS TO STEEL.
  
 2) SHEET M.01: THE AIR BALANCE CALULATION FOR THE
 KITCHEN DOES NOT INCLUDE THE HOOD EXHAUST AND SUPPLY
 CFMS.
  
 3) SHEET M.01: THE CARRIER INFINITY MODEL NO.
 24ANB748A003 IS A 4-TON 17 SEER VARIABLE SPEED UNIT. IT
 IS INCORRECTLY LISTED AS IN THE HVAC SCHEDULES AS A
 5-TON, A 3.75-TON, A 3.25 TON, A 4.75 TON, AND A 2.0
 TON UNIT. PLEASE CORRECT THE SCHEDULES AND CORRECT THE
 ENERGYGAUGE COMPLIANCE FORM WHICH IS ALSO LISTING
 INCORRECT DATA FOR CAPACITIES AND EFFICIENCY RATINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  