Text |
2017-10-27 15:15:52 | 1) SHT. A-00 NOTES 26 BEDS BUT SHT. A-00.1 NOTES THE |
| SLEEPING AREA OCCUPANT LOAD AS 63. CLARIFY. |
| 2) SHT.A-08 - THE CONFIGURATION OF THE ACCESSIBLE |
| SHOWER IN THE ADA SLEEPING ROOM DOES NOT COMPLY WITH |
| THE 2014 FBC-ACCESSIBILITY SEC.608.2.2 (STANDARD |
| ROLL-IN SHOWER) OR 608.2.3 ( ALTERNATE ROLL-IN SHOWER). |
| 3) THE SHOWER SEAT IN THE ACCESSIBLE SHOWER IN THE ADA |
| SLEEPING ROOM SHALL COMPLY WITH 2014 FBC - |
| ACCESSIBILITY SECS 610.3.1 OR 610.3.2. |
| 4) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWER IN THE |
| ADA SLEEPING ROOM SHALL COMPLY WITH 2014 |
| FBC-ACCESSIBILITY SECS. 608.5.2 OR 608.5.3. |
| 5) THE GRAB BARS IN THE ACCESSIBLE SHOWER IN THE ADA |
| SLEEPING ROOM SHALL COMPLY WITH 2014 FBC-ACCESSIBILITY |
| SECS.608.3.2 OR 608.3.3. |
| 6) SHT. A-01 - THE ACCESSIBLE FIGURE NUMBERS ARE FROM |
| AN OUTDATED CODE. PROVIDE THE CORRECT FIGURE NUMBERS |
| FROM THE 2014 FBC-ACCESSIBILITY.WPB AMEND. TO FBC |
| SEC.107.2.1. |
| 7) SHT. P-05 - THE BACK TO BACK SHOWERS IN THE SLEEPING |
| ROOMS ARE NOT VENTED.COMPLY WITH 2014 FBC-PLUMBING |
| SEC.901.2.1. |
| 8) PROVIDE INFORMATION AS TO WHAT STANDARD THE GREASE |
| INTERCEPTOR CALCULATIONS ARE BASED ON. THERE IS NO |
| REFERENCE TO ANY RECOGNIZED STANDARD OR CODE SECTION. |
| 2014 FBC- PLUMBING SEC. 1003.2. |
| 9) SHTS. P-01 & P-02 SHOWS A 4 INCH TEST PORT AND SHT. |
| P-05 SHOWS 3 INCH.CLARIFY. |
| 10) SHOW THE HOT WATER RECIRCULATION LINE ON THE WATER |
| HEATER DETAIL ON SHT. P-08. |
| 11) SHT. A-00 - PROPERTY INFORMATION BOX - THERE IS A |
| NOTE IN THE "OCCUPANT LOAD" AREA THAT REFERS TOSHT. |
| LS-01. THERE IS NO SUCH SHEET IN THESE PLANS. CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |