2017-10-27 15:15:521) SHT. A-00 NOTES 26 BEDS BUT SHT. A-00.1 NOTES THE
 SLEEPING AREA OCCUPANT LOAD AS 63. CLARIFY.
 2) SHT.A-08 - THE CONFIGURATION OF THE ACCESSIBLE
 SHOWER IN THE ADA SLEEPING ROOM DOES NOT COMPLY WITH
 THE 2014 FBC-ACCESSIBILITY SEC.608.2.2 (STANDARD
 ROLL-IN SHOWER) OR 608.2.3 ( ALTERNATE ROLL-IN SHOWER).
 3) THE SHOWER SEAT IN THE ACCESSIBLE SHOWER IN THE ADA
 SLEEPING ROOM SHALL COMPLY WITH 2014 FBC -
 ACCESSIBILITY SECS 610.3.1 OR 610.3.2.
 4) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWER IN THE
 ADA SLEEPING ROOM SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS. 608.5.2 OR 608.5.3.
 5) THE GRAB BARS IN THE ACCESSIBLE SHOWER IN THE ADA
 SLEEPING ROOM SHALL COMPLY WITH 2014 FBC-ACCESSIBILITY
 SECS.608.3.2 OR 608.3.3.
 6) SHT. A-01 - THE ACCESSIBLE FIGURE NUMBERS ARE FROM
 AN OUTDATED CODE. PROVIDE THE CORRECT FIGURE NUMBERS
 FROM THE 2014 FBC-ACCESSIBILITY.WPB AMEND. TO FBC
 SEC.107.2.1.
 7) SHT. P-05 - THE BACK TO BACK SHOWERS IN THE SLEEPING
 ROOMS ARE NOT VENTED.COMPLY WITH 2014 FBC-PLUMBING
 SEC.901.2.1.
 8) PROVIDE INFORMATION AS TO WHAT STANDARD THE GREASE
 INTERCEPTOR CALCULATIONS ARE BASED ON. THERE IS NO
 REFERENCE TO ANY RECOGNIZED STANDARD OR CODE SECTION.
 2014 FBC- PLUMBING SEC. 1003.2.
 9) SHTS. P-01 & P-02 SHOWS A 4 INCH TEST PORT AND SHT.
 P-05 SHOWS 3 INCH.CLARIFY.
 10) SHOW THE HOT WATER RECIRCULATION LINE ON THE WATER
 HEATER DETAIL ON SHT. P-08.
 11) SHT. A-00 - PROPERTY INFORMATION BOX - THERE IS A
 NOTE IN THE "OCCUPANT LOAD" AREA THAT REFERS TOSHT.
 LS-01. THERE IS NO SUCH SHEET IN THESE PLANS. CLARIFY.
  