Plan Review Notes For Permit 17070253 |
Permit Number |
17070253 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-10-30 14:40:17 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17070253 | | 10/30/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS | | FOR THE NEW AC SYSTEMS- SECTION C403.2.1 CALCULATION OF | | HEATING AND COOLING LOADS. | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | APPLICATION FOR THE MECHANICAL PERMIT. | | | | 2) 2ND REQUEST FOR AIR BALANCE CALCULATIONS IN THE | | KITCHEN AND DINING ROOM. | | | | 3) PLEASE PROVIDE A FL. PRODUCT APPROVAL OR A | | MIAMI-DADE NOA FOR THE O/A INTAKE LOUVER- RULE 9N-3 | | FLORIDA ADMINISTRATIVE CODE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|