Plan Review Notes
Plan Review Notes For Permit 17070253
Permit Number 17070253
Review Stop M
Sequence Number 2
Notes
Date Text
2017-10-30 14:40:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070253
 10/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS
 FOR THE NEW AC SYSTEMS- SECTION C403.2.1 CALCULATION OF
 HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT.
  
 2) 2ND REQUEST FOR AIR BALANCE CALCULATIONS IN THE
 KITCHEN AND DINING ROOM.
  
 3) PLEASE PROVIDE A FL. PRODUCT APPROVAL OR A
 MIAMI-DADE NOA FOR THE O/A INTAKE LOUVER- RULE 9N-3
 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  