2017-11-02 08:14:36 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: ALL ITEMS EXCEPT # 4 |
| CORRECTED. SEE ADDITIONAL COMMENTS IN PARANTHESES. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 (RISER DIAGRAM DOES NOT MATCH THE |
| INSTALLATION SHOWN ON THE PLAN. IS THERE AN 800 AMP |
| MAIN THAT FEEDS DISCONNECTS FOR EACH PANEL, OR IS THERE |
| AN MDP PANEL THAT HAS BREAKERS THAT FEED EACH PANEL. A |
| "CT CAN" DOES NOT HAVE ANY OVERCURRENT PROTECTION |
| INSIDE. CLARIFY AND/OR CORRECT DISCREPANCIES BETWEEN |
| PLAN AND RISER DIAGRAM. PROVIDE CALCULATION THAT STATES |
| THE AVAILABLE FAULT CURRENT FOR EACH PANEL. A NOTE IS |
| NOT SUFFICIENT COMPLIANCE. NEC 110.9, 110.10, 215.5; |
| FBC 107.2.1) |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8.CORRECTED. |
| 9. CORRECTED. |
| 10. CORRECTED. |
| 11. CORRECTED. |
| 12. CORRECTED. |
| 13. CORRECTED. |
| 15. CORRECTED. |
| 16. CORRECTED. |
| 17. CORRECTED. |
| 18. CORRECTED. |
| 19. CORRECTED. |
| 20. CORRECTED. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |