Plan Review Notes
Plan Review Notes For Permit 17070253
Permit Number 17070253
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-19 14:54:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BATHROOMS IN THE ACCESSIBLE UNITS DO NOT COMPLY
 WITH FBC ACC 223.2.1 FACILITIES NOT SPECIALIZING IN
 TREATING CONDITIONS THAT AFFECT MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805.
  
 805.4 TOILET AND BATHING ROOMS.
 TOILET AND BATHING ROOMS THAT ARE PROVIDED AS PART OF A
 PATIENT OR RESIDENT SLEEPING ROOM SHALL COMPLY WITH
 603.WHERE PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE
 LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH
 THE APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 PROVIDE DETAIL SHOWING COMPLIANCE WITH ALL ELEMENTS.
 PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. A-01 FIG. #28 IS FOR THE EXCEPTIONN FOR
 RESIDENTIAL DWELLING UNITS AND DOES NOT COMPLY WITH THE
 I2 OCCUPANCY THE ACCESSIBLE TOILETS SHALL COMPLY WITH
 FBC ACC 604.3.2 WITHOUT EXCEPTIO3.
  
 3. THE SHOWERS IN THE ACCESSIBLE BATHROOMS DO NOT
 COMPLY WITH FBC ACC 608.2.1 OR 608.2.2 OR 608.2.3
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 5. ALL GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER FBC ACC 609.4
  
 6. SHT. P-01 THE NOTE ON THE FD IN KITCHEN IS CALLING
 OUT FOR A BACKFLOW PREVENTER THE FD SHALL BE EQUIPPED
 WITH A TRAP PRIMER PLEASE CLARIFY WHAT YOU MEAN BY
 BACKFLOW. PER WPB AMEND TO FBC 107.2.1
  
 7. PLEASE PROVIDE CALCULATIONS FOR GREASE INTERCEPTOR.
 PER WPB AMEND TO FBC 107.2.1
  
 8. THE HORIZONTAL VENTS ON THE WC AND SH IN THE
 ACCESSIBLE BATHROOMS ARE NOT COMPLAINT THOSE FIXTURE
 ARE VENTED BY THE LAVATORY. PER FBC PL 905.3 AND 905.4
  
 9. A TEST PORT OF A MIN OF 4" IS REQUIRED ON THE OUTLET
 OF THE GREASE INTERCEPTOR A 4" TWOWAY CLEAN OUT CAN BE
 USED. PER WPB ORD.
  
 10. TEMPERED WATER IS REQUIRED AT THE LAVATORY'S IN THE
 COMMON BATHROOMS. PER FBC PL 416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125
  
 11. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW AT
 WATER METER PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  