2017-07-17 14:27:28 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| ENERGY CONSERVATION CODES. |
| PERMIT #17070253 |
| 7/17/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 2) PROVIDE AN AIR BALANCE CALCULATION FOR THE KITCHEN |
| AND DINING ROOM AREAS. |
| |
| 3) PLACE A NOTE ON THE PLAN INDICATING THAT SEPARATE |
| PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST AND FIRE |
| SUPPRESSION SYSTEMS. PLEASE NOTE THAT CONDITIONED |
| MAKEUP AIR MAY BE REQUIRED FOR THE HOOD EXHAUST- |
| SECTION 508.1.1. |
| |
| 4) FIRE DAMPERS ARE REQUIRED FOR ALL SUPPLY, RETURN, |
| AND EXHAUST DUCTS AND TRANSFERS THAT ARE PENETRATING |
| THE FIRE-RATED CORRIDOR WALLS, RESIDENT ROOM WALLS, |
| OFFICE WALLS, ETC.- SEE SECTION 607.5.2 & 607.5.3. |
| |
| 5) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR |
| SYSTEMS OF ALL OF THE 5.0 TON AIR HANDLERS PER SECTION |
| 606.2.1. PLEASE NOTE THAT A TYPICAL 5-TON SYSTEM CAN |
| PRODUCE OVER 2000 CFMS OF SUPPLY AIR. PROVIDE SYMBOLS |
| ON THE PLANS TO IDENTIFY THE LOCATIONS OF THE DEVICES. |
| |
| 6) INDICATE HOW ACCESS FOR SERVICE AND REPLACEMENT OF |
| THE AIR HANDLERS ABOVE THE CEILING WILL BE |
| ACCOMPLISHED. SHOW THE LOCATIONS OF ACCESS PANELS AND |
| PROVIDE DETAILS AND DIMENSIONS- SECTION 306.1. |
| |
| 7) VERIFY WITH NOTES, OR PROVIDE CLEARANCE DISTANCE |
| MEASUREMENTS FOR ALL O/A INTAKE OPENINGS TO EXHAUST |
| OUTLETS, PROPERTY LINES, AND DRIVE AREAS SUCH AS |
| DRIVEWAYS OR PARKING LOTS- SECTION 401.4. |
| |
| 8) PROVIDE MOTORIZED OR GRAVITY DAMPERS FOR ALL O/A |
| INTAKE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY |
| CONSERVATION. |
| |
| 9) REFER TO SECTION 506.3.13.2 AND PROVIDE THE REQUIRED |
| CLEARANCE DISTANCE MEASUREMENTS FOR THE HOOD EXHAUST |
| OUTLET. |
| |
| 10) PROVIDE AN ENLARGED KTICHEN PLAN AND EQUIPMENT |
| SCHEDULE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| ALL COOKING APPLIANCES AND THE EXHAUST HOOD. PLEASE |
| NOTE THAT COMBUSTION AIR CALCULATIONS ARE REQUIRED FOR |
| GAS-FIRED APPLIANCES. |
| |
| 11) PROVIDE AN AIR DEVICE SCHEDULE. |
| |
| 12) M-02: SHOW A MEANS OF RETURN AIR FROM GROUP 106, & |
| OFFICES 105, 107, & 108- SECTION 601.5. |
| |
| 13) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER |
| SMACNA STANDARDS. |
| |
| 14) M-04: PROVIDE THE WIND LOAD DESIGN CRITERIA AND |
| STRUCTURAL ENGINEERING FOR INSTALLATION OF THE ROOF TOP |
| CONDENSERS AND ROOF STANDS- SECTION 301.15. SUBMIT A |
| FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE STANDS |
| IF APPLICABLE. |
| |
| 15) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW SYSTEMS.- SECTION C403.2.1 FBC-14 ENERGY |
| CONSERVATION. |
| |
| PLEASE NOTE THAT FURTHER COMMENTS MAY OCCUR AFTER |
| CORRECTED PLANS A RE-SUBMITTED. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |