Plan Review Notes
Plan Review Notes For Permit 17070253
Permit Number 17070253
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-17 14:27:281ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES.
 PERMIT #17070253
 7/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE AN AIR BALANCE CALCULATION FOR THE KITCHEN
 AND DINING ROOM AREAS.
  
 3) PLACE A NOTE ON THE PLAN INDICATING THAT SEPARATE
 PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST AND FIRE
 SUPPRESSION SYSTEMS. PLEASE NOTE THAT CONDITIONED
 MAKEUP AIR MAY BE REQUIRED FOR THE HOOD EXHAUST-
 SECTION 508.1.1.
  
 4) FIRE DAMPERS ARE REQUIRED FOR ALL SUPPLY, RETURN,
 AND EXHAUST DUCTS AND TRANSFERS THAT ARE PENETRATING
 THE FIRE-RATED CORRIDOR WALLS, RESIDENT ROOM WALLS,
 OFFICE WALLS, ETC.- SEE SECTION 607.5.2 & 607.5.3.
  
 5) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF ALL OF THE 5.0 TON AIR HANDLERS PER SECTION
 606.2.1. PLEASE NOTE THAT A TYPICAL 5-TON SYSTEM CAN
 PRODUCE OVER 2000 CFMS OF SUPPLY AIR. PROVIDE SYMBOLS
 ON THE PLANS TO IDENTIFY THE LOCATIONS OF THE DEVICES.
  
 6) INDICATE HOW ACCESS FOR SERVICE AND REPLACEMENT OF
 THE AIR HANDLERS ABOVE THE CEILING WILL BE
 ACCOMPLISHED. SHOW THE LOCATIONS OF ACCESS PANELS AND
 PROVIDE DETAILS AND DIMENSIONS- SECTION 306.1.
  
 7) VERIFY WITH NOTES, OR PROVIDE CLEARANCE DISTANCE
 MEASUREMENTS FOR ALL O/A INTAKE OPENINGS TO EXHAUST
 OUTLETS, PROPERTY LINES, AND DRIVE AREAS SUCH AS
 DRIVEWAYS OR PARKING LOTS- SECTION 401.4.
  
 8) PROVIDE MOTORIZED OR GRAVITY DAMPERS FOR ALL O/A
 INTAKE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 9) REFER TO SECTION 506.3.13.2 AND PROVIDE THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FOR THE HOOD EXHAUST
 OUTLET.
  
 10) PROVIDE AN ENLARGED KTICHEN PLAN AND EQUIPMENT
 SCHEDULE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 ALL COOKING APPLIANCES AND THE EXHAUST HOOD. PLEASE
 NOTE THAT COMBUSTION AIR CALCULATIONS ARE REQUIRED FOR
 GAS-FIRED APPLIANCES.
  
 11) PROVIDE AN AIR DEVICE SCHEDULE.
  
 12) M-02: SHOW A MEANS OF RETURN AIR FROM GROUP 106, &
 OFFICES 105, 107, & 108- SECTION 601.5.
  
 13) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SMACNA STANDARDS.
  
 14) M-04: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 STRUCTURAL ENGINEERING FOR INSTALLATION OF THE ROOF TOP
 CONDENSERS AND ROOF STANDS- SECTION 301.15. SUBMIT A
 FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE STANDS
 IF APPLICABLE.
  
 15) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS.- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 PLEASE NOTE THAT FURTHER COMMENTS MAY OCCUR AFTER
 CORRECTED PLANS A RE-SUBMITTED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  