2017-07-18 15:04:32CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHEET E-01, NOTE 1 REFERENCES THE 2013 NATIONAL
 ELECTRICAL CODE (NEC), WHICH DOESN'T EXIST. REVISE
 REFERENCE TO THE CURRENT CODE, WHICH IS THE 2011 NEC.
 FBC PREFACE.
 2. SHEET E-01, NOTE 4 STATES THAT ALL RECEPTACLES SHALL
 BE TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION
 DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12
 3. SHEET E-09, PANEL SCHEDULES FOR PANELS A, B, C, D,
 AND K STATE THAT THEY ARE 120/240 SINGLE PHASE PANELS.
 THEY ARE FED FROM A 120/208 SYSTEM, SO THEY SHOULD BE
 LABELED AS 120/208 SINGLE PHASE PANELS. THE CORRECT
 VOLTAGE SHOULD BE USED IN ALL LOAD CALCULATIONS AND
 SHORT CIRCUIT CALCULATIONS FOR THE PANELS. PROVIDE
 CORRECTION FOR ALL PANEL SCHEDULES AND PANELS IN RISER
 DIAGRAM. FBC 107.2.1; NEC 220.5, 215.5
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
 6. RISER DIAGRAM SHOWS A GROUNDING ELECTRODE
 CONDUCTOR(GEC) TO 2 GROUND RODS. REVISE RISER DIAGRAM
 TO SHOW ALL GROUNDING ELECTRODES AVAILABLE AND THE GEC
 SIZE TO EACH. NEC 250.50, 250.66
 7. CIRCUIT NUMBERS FOR LIGHTING ARE NOT IDENTIFIED ON
 ANY OF THE LIGHTING PLANS. PROVIDE CORRECTION. FBC
 107.2.1, NEC 215.5
 8. PROVIDE DETAIL OF EXTERIOR LIGHTING CONTROLS FOR
 PORTE COCHERE PER ENERGY CODE: "LIGHTING NOT DESIGNATED
 FOR DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY
 EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME
 SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS." FBC ENERGY
 C405.2.4
 9. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 OCCUPANCY SENSORS REQUIRED. FBC C405.2.2, 405.2.2.2
 10. WILL THERE BE ANY PATIENT CARE AREAS? PLEASE
 INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED PER NEC
 517.13.
 11. PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED
 LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC
 MECHANICAL CODE M306.3.1
 12. PROVIDE KITCHEN EQUIPMENT SCHEDULE SHOWING CURRENT
 REQUIREMENTS FOR EACH APPLIANCE AND LISTING. NEC 110.3;
 FBC 107.2.1
 13. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN
 HOODS ETC. A NOTE WILL SUFFICE.
 14. SHOW ON PLAN THE LOCATION OF PANEL K. FBC 107.2.1
 15. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN KITCHEN.
 NEC 210.8(B)(2)
 16. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 17. SHEET E-02, THE CIRCUIT FOR THE WATER FEATURE IS
 NOT INDICATED. PROVIDE CORRECTION. FBC 107.2.1; NEC
 215.5
 18. PROVIDE COMPLIANCE WITH VOLTAGE DROP REQUIREMENTS
 OF THE ENERGY CODE. FBC C405.7.3
 19. AE TYPE FIXTURES SHOWN ON LIGHTING PLANS ARE
 CONTROLLED BY A SWITCH. WHEN THE SWITCH IS TURNED OFF,
 THE LIGHTS WILL THEN USE THE BATTERY BACKUP TO POWER
 THE LIGHT, THUS DEFEATING THE PURPOSE OF AN EMERGENCY
 LIGHTING SYSTEM. PROVIDE CORRECTION. NEC 700.12(F)
 20. PROVIDE DETAIL OF INTERIOR LIGHTING POWER
 ALLOWANCES, EITHER BY BUILDING TYPE OR BY AREA METHOD
 AS EXPLAINED IN THE FBC ENERGY CODE, WITH EXPLANATION
 OF THE TOTAL AMOUNT OF LIGHTING POWER PROPOSED TO MEET
 CODE REQUIREMENTS. FBC 405.5.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  