2017-07-18 15:04:32 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. SHEET E-01, NOTE 1 REFERENCES THE 2013 NATIONAL |
| ELECTRICAL CODE (NEC), WHICH DOESN'T EXIST. REVISE |
| REFERENCE TO THE CURRENT CODE, WHICH IS THE 2011 NEC. |
| FBC PREFACE. |
| 2. SHEET E-01, NOTE 4 STATES THAT ALL RECEPTACLES SHALL |
| BE TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION |
| DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12 |
| 3. SHEET E-09, PANEL SCHEDULES FOR PANELS A, B, C, D, |
| AND K STATE THAT THEY ARE 120/240 SINGLE PHASE PANELS. |
| THEY ARE FED FROM A 120/208 SYSTEM, SO THEY SHOULD BE |
| LABELED AS 120/208 SINGLE PHASE PANELS. THE CORRECT |
| VOLTAGE SHOULD BE USED IN ALL LOAD CALCULATIONS AND |
| SHORT CIRCUIT CALCULATIONS FOR THE PANELS. PROVIDE |
| CORRECTION FOR ALL PANEL SCHEDULES AND PANELS IN RISER |
| DIAGRAM. FBC 107.2.1; NEC 220.5, 215.5 |
| 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 5. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| AVAILABLE PER NEC 110.24. |
| 6. RISER DIAGRAM SHOWS A GROUNDING ELECTRODE |
| CONDUCTOR(GEC) TO 2 GROUND RODS. REVISE RISER DIAGRAM |
| TO SHOW ALL GROUNDING ELECTRODES AVAILABLE AND THE GEC |
| SIZE TO EACH. NEC 250.50, 250.66 |
| 7. CIRCUIT NUMBERS FOR LIGHTING ARE NOT IDENTIFIED ON |
| ANY OF THE LIGHTING PLANS. PROVIDE CORRECTION. FBC |
| 107.2.1, NEC 215.5 |
| 8. PROVIDE DETAIL OF EXTERIOR LIGHTING CONTROLS FOR |
| PORTE COCHERE PER ENERGY CODE: "LIGHTING NOT DESIGNATED |
| FOR DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY |
| EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME |
| SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING |
| DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| OF POWER FOR A PERIOD OF AT LEAST 10 HOURS." FBC ENERGY |
| C405.2.4 |
| 9. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| OCCUPANCY SENSORS REQUIRED. FBC C405.2.2, 405.2.2.2 |
| 10. WILL THERE BE ANY PATIENT CARE AREAS? PLEASE |
| INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED PER NEC |
| 517.13. |
| 11. PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED |
| LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC |
| MECHANICAL CODE M306.3.1 |
| 12. PROVIDE KITCHEN EQUIPMENT SCHEDULE SHOWING CURRENT |
| REQUIREMENTS FOR EACH APPLIANCE AND LISTING. NEC 110.3; |
| FBC 107.2.1 |
| 13. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN |
| HOODS ETC. A NOTE WILL SUFFICE. |
| 14. SHOW ON PLAN THE LOCATION OF PANEL K. FBC 107.2.1 |
| 15. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN KITCHEN. |
| NEC 210.8(B)(2) |
| 16. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2 |
| AND ASHREA 90.1: 8.4.2 |
| 17. SHEET E-02, THE CIRCUIT FOR THE WATER FEATURE IS |
| NOT INDICATED. PROVIDE CORRECTION. FBC 107.2.1; NEC |
| 215.5 |
| 18. PROVIDE COMPLIANCE WITH VOLTAGE DROP REQUIREMENTS |
| OF THE ENERGY CODE. FBC C405.7.3 |
| 19. AE TYPE FIXTURES SHOWN ON LIGHTING PLANS ARE |
| CONTROLLED BY A SWITCH. WHEN THE SWITCH IS TURNED OFF, |
| THE LIGHTS WILL THEN USE THE BATTERY BACKUP TO POWER |
| THE LIGHT, THUS DEFEATING THE PURPOSE OF AN EMERGENCY |
| LIGHTING SYSTEM. PROVIDE CORRECTION. NEC 700.12(F) |
| 20. PROVIDE DETAIL OF INTERIOR LIGHTING POWER |
| ALLOWANCES, EITHER BY BUILDING TYPE OR BY AREA METHOD |
| AS EXPLAINED IN THE FBC ENERGY CODE, WITH EXPLANATION |
| OF THE TOTAL AMOUNT OF LIGHTING POWER PROPOSED TO MEET |
| CODE REQUIREMENTS. FBC 405.5.2 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |