Date |
Text |
2017-07-25 17:20:29 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070253 |
| ADD: 1803 S. AUSTRALIAN AVE. |
| CONT: DRY ART CONSTRUCTION |
| TEL: 561-436-3703 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JULY 24TH/ 2017 |
| ACTION: DENIED |
| |
| 1) THE SURVEY SUBMITTED BY PM SURVEYING LIST THIS |
| PROPERTY IN A B FLOOD ZONE. USING THE ADOPTED FIRM MAPS |
| DATED MARCH 1, 1979 COMMUNITY PANEL NUMBER 120229 0020 |
| B THIS SITE IS LOCATED IN AN A-9 FLOOD ZONE THE |
| FREEBOARD AT THAT TIME WOULD HAVE BEEN AN ADDITIONAL 6 |
| INCHES OR FINISH FLOOR ABOVE 13 FOOT 6 INCHES. THIS |
| BUILDING IS CONSIDERED A POST FIRM BUILDING WITH THE |
| PERMIT APPLICATION FOR THIS BUILDING DATED 10/19/79. |
| THE BUILDING AT THAT TIME WAS ALSO ADDRESSED OFF OF |
| (OLD) OKEECHOBEE RD., 1501 OLD OKEECHOBEE RD. THIS |
| BUILDING IS TO BE CONSIDERED SUBSTANTIAL IMPROVEMENT AS |
| WELL SINCE THE PROPERTY APPRAISERS OFFICE LIST THE |
| IMPROVED VALUE OF THIS BUILDING AT $687,288.00 DOLLARS |
| IN VALUE AND THE RENOVATION AND ADDITION ARE VALUED AT |
| OVER 50% OF THE APPRAISED (PALM BEACH COUNTY PROPERTY |
| APPRAISERS OFFICE) BUILDING VALUE. PLEASE PROVIDE A NEW |
| SURVEY SHOWING THE PROPERTY IN AN A9 FLOOD ZONE AND |
| PLEASE PROVIDE A FLOOD ZONE CERTIFICATE. PLEASE MAKE |
| REFERENCE TO ELEVATIONS IN NGVD 29, THE CITY IS STILL |
| USING THIS REFERENCE UNTIL AUGUST 28/ 2017 WHEN THE NEW |
| MAPS WILL BE ADOPTED AND A 2 FOOT FREEBOARD |
| REQUIREMENT. |
| |
| FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION |
| IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS, |
| ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL. |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. |
| W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| JURISDICTION. |
| FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| OMB NO. 1660-0008 |
| EXPIRATION DATE: NOV. 30/2018 |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 2) DISCREPANCY IN OCCUPANT LOADS. THE COVERSHEET A-00 |
| LIST THE OCCUPANT LOAD FOR THE I-2 OCCUPANCY 10,373 SQ. |
| FT./ 240= 44 OCCUPANTS WHEREAS THE LIFE SAFETY SHEET |
| LIST THE TOTAL AMOUNT OF OCCUPANTS AT 75 OCCUPANTS. THE |
| LIFE SAFETY SHEET HAS THE CORRECT OCCUPANT LOAD AND |
| CALCULATIONS. PLEASE UPDATE THE PLANS SEE 2014 FBC-B |
| TABLE 1004.1.2 |
| |
| 3) WITH THE OCCUPANT LOAD OF 50 OR MORE IN I-2 |
| OCCUPANCY THE RISK CATEGORY OF THE BUILDING IS |
| INCREASED TO A RISK CATEGORY III AND WIND SPEED TO 180 |
| MPH VULT. GROUP I-2 OCCUPANCIES WITH AN OCCUPANT LOAD |
| OF 50 OR MORE RESIDENT CARE RECIPIENTS BUT NOT HAVING |
| SURGERY OR EMERGENCY TREATMENT FACILITIES, IF THE |
| FACILITY DOES HAVE SURGERY OR EMERGENCY TREATMENT |
| FACILITIES THEN THE STRUCTURES RISK CATEGORY BECOMES AN |
| IV. |
| |
| 4A) THE OTHER ISSUE THE FRONT COVER SHEET A00 LIST THIS |
| STRUCTURE AS A B EXPOSURE. TO THE NORTHEAST THERE IS A |
| C SURFACE ROUGHNESS AS WELL AS TO THE SOUTH AND |
| SOUTHEAST. SEE THE 2014 FBC-B EXPOSURE CATEGORY |
| 1609.4.2 SURFACE ROUGHNESS. THIS SURFACE ROUGHNESS |
| SHALL APPLY TO ANY BUILDING LOCATED WITHIN SURFACE |
| ROUGHNESS B TYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF |
| SURFACE ROUGHNESS C OR D TYPE TERRAIN THAT EXTENDS MORE |
| THAN 600 FEET IN THE UPWIND DIRECTION AND WIDTH GREATER |
| THAN 150 FEET. |
| |
| 4B) THE ADJUSTMENT FACTORS WILL COME INTO PLAY WITH THE |
| ASSOCIATED PRESSURES FOR A C EXPOSURE, SEE TABLE |
| 1609.7(2) ADJUSTMENT FACTORS FOR BUILDING HEIGHT AND |
| EXPOSURE. |
| |
| 5) SHEET A-00: |
| 5A) THE SITE PLAN PROVIDED SHOWS 31 PARKING SPACES ONLY |
| ONE OF THE SPACES IS AN ACCESSIBLE PARKING SPACE WITH |
| ACCESS AISLE. THE 2014 FBC-ACCESSIBILITY CODE TABLE |
| 208.2 PARKING SPACES REQUIRES 2 ACCESSIBLE PARKING |
| SPACES AND ACCESS AISLES FOR 26 TO 50 PARKING SPACES. |
| |
| 5B) THE SITE PLAN ALSO SHOWS THE PARKING SPACES 18 AND |
| 19 TO BE UNDER THE PORTE COCHERE BUT NOT THE ACCESSIBLE |
| PARKING STALL. THE PLAN DOES NOT PROVIDE EQUIVALENT |
| FACILITATION SECTION 103 OF THE ACCESSIBILITY CODE. IF |
| COVERED PARKING IS PROVIDED THEN AT LEAST ONE |
| ACCESSIBLE SPACE IS REQUIRED TO BE ALSO UNDER THE PORT |
| COCHERE OR AN EQUIVALENCY TO. |
| |
| 5C) WITH THE REQUIREMENT OF A NEW ACCESSIBLE PARKING |
| SPACE PLEASE PROVIDE COMPLIANCE WITH THE 2014 |
| FBC-ACCESSIBILITY CODE 502.4 GROUND SURFACES 502.4 |
| FLOOR OR GROUND SURFACES. |
| PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL |
| COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME |
| LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN |
| LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES NOT STEEPER |
| THAN 1:48 SHALL BE PERMITTED. |
| |
| 5D)(1) WITH THE ADDITION OF THE PORTE COCHERE PLEASE |
| ALSO NOTE THIS BEING A DROP OFF ZONE WILL NEED TO SHOW |
| COMPLIANCE WITH THE ACCESS. CODE 209.2.1 PASSENGER |
| LOADING ZONES. PASSENGER LOADING ZONES, EXCEPT THOSE |
| REQUIRED TO COMPLY WITH 209.2.2 AND 209.2.3, SHALL |
| PROVIDE AT LEAST ONE PASSENGER LOADING ZONE COMPLYING |
| WITH 503 IN EVERY CONTINUOUS 100 LINEAR FEET (30 M) OF |
| LOADING ZONE SPACE, OR FRACTION THEREOF. |
| |
| 5D)(2) 2014 FBC-ACCESS. CODE 209.3 MEDICAL CARE AND |
| LONG-TERM CARE FACILITIES. AT LEAST ONE PASSENGER |
| LOADING ZONE COMPLYING WITH 503 SHALL BE PROVIDED AT AN |
| ACCESSIBLE ENTRANCE TO LICENSED MEDICAL CARE AND |
| LICENSED LONG-TERM CARE FACILITIES WHERE THE PERIOD OF |
| STAY EXCEEDS TWENTY-FOUR HOURS. |
| |
| 5E) THE SITE PLAN SHOWS (2) NEW SIDEWALKS THAT ENTER |
| THE BUILDING. PLEASE PROVIDE THE SLOPES FOR THE |
| SIDEWALKS DO THEY RISE FROM THE PARKING LOT TO THE NEW |
| LANDING NEXT TO THE DOORS? PLEASE PROVIDE THE CHANGE IN |
| GRADE AND CROSS SLOPES? ARE THESE SIDEWALKS TO BE |
| CONSIDERED RAMPS BECAUSE OF THE ELEVATION CHANGE? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE |
| TO DETERMINE CODE COMPLIANCE. |
| |
| 6) SHEET A-02; |
| 6A) PLEASE NOTE THE WALL LEGEND SHOWS A CROSSED HATCHED |
| WALL AS A 1 HOUR FIRE RATED ASSEMBLY, WHEREAS SHEETS |
| A-03 & A-04 BOTH SHOW THESE WALLS TYPES AS NEW GYPSUM |
| PARTITIONS. PLEASE PROVIDE HOW COMPLIANCE WITH FBC-B |
| 407.5 SMOKE BARRIERS. SMOKE BARRIERS SHALL BE PROVIDED |
| TO SUBDIVIDE EVERY STORY USED BY PERSONS RECEIVING |
| CARE, TREATMENT OR SLEEPING AND TO DIVIDE OTHER STORIES |
| WITH AN OCCUPANT LOAD OF 50 OR MORE PERSONS, INTO NO |
| FEWER THAN TWO SMOKE COMPARTMENTS. 407.3 CORRIDOR WALL |
| CONSTRUCTION. |
| CORRIDOR WALLS SHALL BE CONSTRUCTED AS SMOKE PARTITIONS |
| IN ACCORDANCE WITH SECTION 710. |
| |
| 6B) PLEASE PROVIDE HOW COMPLIANCE WITH FBC-B 407.4.3.5 |
| CARE SUITES CONTAINING SLEEPING ROOM AREAS. |
| SLEEPING ROOMS SHALL BE PERMITTED TO BE GROUPED INTO |
| CARE SUITES WITH ONE INTERVENING ROOM IF ONE OF THE |
| FOLLOWING CONDITIONS IS MET: |
| 1. THE INTERVENING ROOM WITHIN THE CARE SUITE IS NOT |
| USED AS AN EXIT ACCESS FOR MORE THAN EIGHT CARE |
| RECIPIENT BEDS. |
| 2. THE ARRANGEMENT OF THE CARE SUITE ALLOWS FOR DIRECT |
| AND CONSTANT VISUAL SUPERVISION BY CARE |
| PROVIDERS. |
| |
| 6C) PLEASE PROVIDE CALCULATIONS FOR COMPLYING WITH |
| FBC-B 407.5.1 REFUGE AREA. |
| |
| 7A) NEITHER SHEET A-00.1 NOR A-01 SHOW COMPLIANCE WITH |
| THE 2014 ACCESSIBILITY CODE 223.2 DETOXIFICATION |
| FACILITIES SHALL HAVE AT LEAST 10 % BUT NOT FEWER THAN |
| ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE |
| MOBILITY FEATURES COMPLYING WITH 805. |
| |
| 7B) ACCESSIBILITY CODE 805.2 TURNING SPACE. |
| |
| 7C) 805.3 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| COMPLYING WITH 305 SHALL BE PROVIDED ON EACH SIDE OF |
| THE BED. A CLEAR FLOOR SPACE SHALL BE POSITIONED FOR A |
| PARALLEL APPROACH TO THE SIDE OF THE BED. |
| |
| 7D) 805.4. TOILET & BATHING ROOMS TOILET AND BATHING |
| ROOMS THAT ARE PART OF THE PATIENT OR RESIDENT SLEEPING |
| ROOM SHALL COMPLY WITH 603. WHERE PROVIDED, NO FEWER |
| THAN ONE WATER CLOSET, ONE LAVATORY, AND ONE BATHTUB OR |
| SHOWER SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF |
| 603 THROUGH610. |
| |
| 7E) THE PLANS DO NOT PROVIDE COMPLIANCE FOR ACCESSIBLE |
| SIGNAGE AS PER REQUIRED PER SECTION 216.1 OF THE |
| ACCESSIBILITY CODE. SIGNS SHALL BE PROVIDED IN |
| ACCORDANCE WITH ALL OF SECTION 216 AND SHALL COMPLY |
| WITH 703. |
| |
| 8) SHEETS A-06, A-07, A-09 & S-01 ARE ALL IN VULT FOR |
| 170 MPH EXPOSURE B. ALSO SEE COMMENT # 3. PLEASE UPDATE |
| THE PLANS TO THE 180 VULT, EXPOSURE C AND THE N CONVERT |
| PRESSURES INTO VASD SINCE THE PRODUCT APPROVALS ARE ALL |
| IN VASD. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 9) / 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. NOA |
| 16-0629.16 COMPLY WITH COMMENT #10 |
| (B) WINDOWS & MULLIONS FL 14604.8 PROVIDE THE FLORIDA |
| REPORT COVERSHEET!!!!!!!!!! (A) |
| 14608.3 PROVIDE THE FLORIDA REPORT COVERSHEET!!!!!!!!!! |
| (B) ONLY ONE REPORT SUBMITTED |
| 14632.5 PROVIDE THE FLORIDA REPORT COVERSHEET!!!!!!!!!! |
| SEE COMMENT # 10 COMPLY |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| VENTILATORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 10) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 11) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, |
| THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE |
| AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| SPECIFIC SITE. |
| |
| 12) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 13) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| ON SUBSEQUENT REVIEWS. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| |