Plan Review Notes For Permit 17070230 |
Permit Number |
17070230 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-13 02:46:32 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE HEAT PUMP.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 2) THE HEAT PUMP SHALL COMPLY WITH 2014 FBC-ENERGY SEC. | | R403.9.1 - REQD. ON-OOF SWITCH MOUNTEDD ON OUTSIDE OF | | HEATER. | | 3) THE HEAT PUMP SHALL HAVE A MINIMUM COP OF 4.0 WHEN | | TESTED IN ACCORDANCE WITH AHRI 1160. 2014 FBC-ENERGY | | SEC. R403.9.1.2. | | 4) TIME SWITCHES OR OTHER CONTROL METHOD TO | | AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS | | ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON | | ALL HEATERS AND PUMPS. 2014 FBC-ENERGY | | SEC.R403.9.2.(SEE EXCEPTION #3 ALSO). | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|