Plan Review Notes For Permit 17070187 |
Permit Number |
17070187 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-11-29 09:21:18 | MECHANICAL PROVISOS: | | | | 1) PROVIDE A REVISED DUAL FUEL VENTILATION DETAIL WITH | | THE CORRECT UL1978 LISTING, AND THE "ZERO CLEARANCE | | GREASE DUCT" NOTE REMOVED. | | | | 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | INSTRUCTIONS FOR THE PIZZA OVEN AND THE GREASE DUCT | | MUST BE ONSITE AT TIME OF INSPECTION. | | | | 3) LIGHT TEST FOR GREASE DUCT REQUIRED- SECTION | | 506.3.2.5. | | | | CCOLE- 11/30/17 | | |
|