Plan Review Notes
Plan Review Notes For Permit 17070187
Permit Number 17070187
Review Stop M
Sequence Number 2
Notes
Date Text
2017-11-29 09:21:18MECHANICAL PROVISOS:
  
 1) PROVIDE A REVISED DUAL FUEL VENTILATION DETAIL WITH
 THE CORRECT UL1978 LISTING, AND THE "ZERO CLEARANCE
 GREASE DUCT" NOTE REMOVED.
  
 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE PIZZA OVEN AND THE GREASE DUCT
 MUST BE ONSITE AT TIME OF INSPECTION.
  
 3) LIGHT TEST FOR GREASE DUCT REQUIRED- SECTION
 506.3.2.5.
  
 CCOLE- 11/30/17
  