Plan Review Notes
Plan Review Notes For Permit 17070187
Permit Number 17070187
Review Stop E
Sequence Number 2
Notes
Date Text
2017-11-29 07:30:33APPROVED WITH EXCEPTION. BREAKER SIZE FEEDING PANEL C
 AND PANEL P ARE LIMITED TO 60 AMP FOR WIRE SIZE SHOWN.