2017-11-30 08:13:40***PROVIDE DETAIL AT INSPECTION - REVISION REQUIRED IF
 REQUESTED BY INSPECTOR***
 **ISSUED AT APPLICANT'S RISK**
  
 1. REVISE THE "DUAL FUEL VENTILATION" DETAIL ON SHEET
 3.3M:
  
 A. NO SPEC FOR THE ANCHORS OTHER THAN "EYEBOLTS"
 (LACKING SIZE, MATERIAL, MINIMUM EMBEDMENT, TYPE OF
 EYEBOLT).
  
 B. SUBSTRATE NOT CLEAR; SPEC INDICATES "MASONRY
 ANCHORED EYEBOLTS" BUT DOES NOT INDICATE DECK TYPE,
 REVISE TO INCLUDE. SPEC IMPLIES THAT THE SUBSTRATE IS
 "MASONRY" - DO YOU MEAN CONCRETE?
  
 C. SPEC STATES "PITCH POCKETS" AFTER ANCHOR BOLTS;
 PROVIDE A DETAIL, INSTALLATION SPEC IS NOT CLEAR.
  
  