Plan Review Notes For Permit 17070187 |
Permit Number |
17070187 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-11-30 08:13:40 | ***PROVIDE DETAIL AT INSPECTION - REVISION REQUIRED IF | | REQUESTED BY INSPECTOR*** | | **ISSUED AT APPLICANT'S RISK** | | | | 1. REVISE THE "DUAL FUEL VENTILATION" DETAIL ON SHEET | | 3.3M: | | | | A. NO SPEC FOR THE ANCHORS OTHER THAN "EYEBOLTS" | | (LACKING SIZE, MATERIAL, MINIMUM EMBEDMENT, TYPE OF | | EYEBOLT). | | | | B. SUBSTRATE NOT CLEAR; SPEC INDICATES "MASONRY | | ANCHORED EYEBOLTS" BUT DOES NOT INDICATE DECK TYPE, | | REVISE TO INCLUDE. SPEC IMPLIES THAT THE SUBSTRATE IS | | "MASONRY" - DO YOU MEAN CONCRETE? | | | | C. SPEC STATES "PITCH POCKETS" AFTER ANCHOR BOLTS; | | PROVIDE A DETAIL, INSTALLATION SPEC IS NOT CLEAR. | | | | |
|