2017-11-03 10:08:51 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17070187 | | 11/3/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE SELECTED B-VENT CANNOT BE USED AS A GREASE | | EXHAUST DUCT FOR THE PIZZA OVEN. PLEASE REVIEW THE | | PIZZA OVEN VENTING OPTIONS ON THE FRONT SHEET WHICH | | INDICATES TWO METHODS- DIRECT VENTING WITH 8 INCH | | "CHIMNEY" PIPE LISTED TO UL 103HT AND INSTALLED PER UL | | 737, OR ATYPE 1 HOOD SYSTEM AND GREASE EXHAUST DUCT. | | THE UL 103 HT LISTED DUCTS TYPICALLY ALSO CARRY THE UL | | 1978 LISTING APPLIED TO FACTORY BUILT GREASE DUCTS- SEE | | SECTION 506.3 & 506.3.1.1., AND IN SOME CASES CARRY THE | | UL 2221 LISTING APPLIED TO GREASE DUCT ENCLOSURES- SEE | | SECTION 506.3.11.3. | | | | 2) REFER TO SECTION 7.8.2 NFPA 96 ROOFTOP TERMINATIONS | | ITEMS 1-9 AND SHOW COMPLIANCE. PLEASE NOTE THAT AN | | EXHAUST FAN IS REQUIRED PER ITEMS #8 & 9. PLEASE REVIEW | | THE MUGNAINI WEBSITE WHICH PROVIDES OPTIONS FOR EXHAUST | | DUCTS AND FANS, | | | | 3) SHEET 3.4M: VERIFY THE TERMINATION LOCATION OF THE | | GREASE DUCT IS NOT WITHIN 10' OF THE ROOF EDGE OR | | PROVIDE A GUARD IF THE EXISTING PARAPET IS LESS THAN | | 42". | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|