Plan Review Notes
Plan Review Notes For Permit 17070187
Permit Number 17070187
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-02 10:18:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. WHAT IS RATING OF METER CAN BEING INSTALLED? PROVIDE
 SPEC SHEETS. NEC 110.3
 2. PANEL A DOES NOT SHOW LOAD OF PANEL P. INCLUDE ALL
 LOADS IN PANEL A SCHEDULE. NEC 215.2, 408.30; FBC
 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, SHOW CURRENT
 DRAW FOR EACH PHASE. IT APPEARS THAT THE STATED 500
 KCMIL SERVICE IS OVERLOADED. CLARIFY AND/OR CORRECT AS
 NEEDED. NEC 215.2, 220, 230.42; FBC 107.2.1
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE NOTE FOR MARKING OF HI-LEG PER CODE. NEC
 110.15, 408.3(E) AND (F)(1)
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PIECE OF SERVICE EQUIPMENT AND THE DOWNSTREAM PANELS.
 INCLUDE INFORMATION FROM THE POWER COMPANY STATING WHAT
 THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE
 TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 7. WIRING FROM DISCONNECT A TO PANEL A REQUIRES AN EGC.
 PROVIDE CORRECTION. NEC 250.122
 8. PROVIDE PANEL SCHEDULE FOR BREWHOUSE PANEL TO
 CONFIRM SIZING AND AIC RATINGS. NEC 110.3, 110.10,
 408.4, 408.30; FBC 107.2.1
 9. CLARIFY LOCATION FOR PANEL A AND PANEL B. IT APPEARS
 THAT THEY OCCUPY THE SAME SPACE IN A WALL. PROVIDE
 CORRECTION IF NECESSARY. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  