2017-11-02 10:18:10 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. WHAT IS RATING OF METER CAN BEING INSTALLED? PROVIDE |
| SPEC SHEETS. NEC 110.3 |
| 2. PANEL A DOES NOT SHOW LOAD OF PANEL P. INCLUDE ALL |
| LOADS IN PANEL A SCHEDULE. NEC 215.2, 408.30; FBC |
| 107.2.1 |
| 3. PROVIDE LOAD CALCULATION FOR SERVICE, SHOW CURRENT |
| DRAW FOR EACH PHASE. IT APPEARS THAT THE STATED 500 |
| KCMIL SERVICE IS OVERLOADED. CLARIFY AND/OR CORRECT AS |
| NEEDED. NEC 215.2, 220, 230.42; FBC 107.2.1 |
| 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 5. PROVIDE NOTE FOR MARKING OF HI-LEG PER CODE. NEC |
| 110.15, 408.3(E) AND (F)(1) |
| 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PIECE OF SERVICE EQUIPMENT AND THE DOWNSTREAM PANELS. |
| INCLUDE INFORMATION FROM THE POWER COMPANY STATING WHAT |
| THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE |
| TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, |
| 110.10 |
| 7. WIRING FROM DISCONNECT A TO PANEL A REQUIRES AN EGC. |
| PROVIDE CORRECTION. NEC 250.122 |
| 8. PROVIDE PANEL SCHEDULE FOR BREWHOUSE PANEL TO |
| CONFIRM SIZING AND AIC RATINGS. NEC 110.3, 110.10, |
| 408.4, 408.30; FBC 107.2.1 |
| 9. CLARIFY LOCATION FOR PANEL A AND PANEL B. IT APPEARS |
| THAT THEY OCCUPY THE SAME SPACE IN A WALL. PROVIDE |
| CORRECTION IF NECESSARY. FBC 107.2.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |