2017-10-31 10:29:32 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17070187 |
| W. P. B. PERMIT: 16120091 |
| ADD: 332 EVERNIA ST. |
| CONT: MONTEIRO DEVELOPMENT INC. |
| TEL: 561-346-6916 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. OCT. 31/ 2017 |
| ACTION: DENIED |
| |
| 1) THE SHEET 3.1 SHOWS A NEW PIZZA OVEN, THERE WILL BE |
| MANY COMMENTS ABOUT THE USE AND LISTING OF THE OVEN AND |
| VENTING. UNDER THE BUILDING CODE, 2014 FBC-B PLEASE |
| PROVIDE HOW HIGH THE VENT WILL PENETRATE THE ROOF, WE |
| WILL ALSO NEED TO KNOW THE HEIGHT OF THE PARAPET IN |
| THIS AREA AS WELL AS THE HEIGHT OF THE OVERALL VENT AND |
| IF THE VENT WILL REQUIRE, GUIDE WIRES FOR THE WIND AND |
| HOW TO ANCHOR THE WIRES/ SUPPORTS TO THE ROOF AND TO |
| THE VENT ITSELF. |
| LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 2) PLEASE PROVIDE WHAT TYPE OF ROOF PENETRATION WILL BE |
| MADE FOR THE STRUCTURAL DECK, AND HOW WILL THE OPENING |
| AND VENT BE PROTECTED FROM WATER INTRUSION. |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |