Plan Review Notes
Plan Review Notes For Permit 17070184
Permit Number 17070184
Review Stop G
Sequence Number 1
Notes
Date Text
2017-07-11 05:12:131) I HAVE RESEARCHED CITY RECORDS BACK TO 1996 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 AN LP TANK. WHAT OTHER APPLIANCES/EQUIPMENT IS SUPPLIED
 BY THIS "EXISTING " TANK? SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE LP TANK, THE TANK MUST BE INCLUDED IN
 THIS PERMIT FOR THIS SCOPE OF WORK. WPB AMEND. TO FBC
 SEC. 105.1.
 2) PROVIDE THE SIZE AND TYPE OF THE HOLD-DOWN
 CABLES/STRAPS FOR THE TANK AND SUBMIT ANCHORING DETAILS
 FOR THE LP TANK. NFPA 58-11 SEC. 5.2.4.3.
 3) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 GENERATOR AND SHOW THE TYPE OF PIPE MATERIAL. THE PIPE
 SHALL BE SIZED IN ACCORDANCE WITH THE SPECIFIC SIZING
 TABLES LISTED IN 2014 FBC-FUEL GAS TABLES 402.4 (25)
 THROUGH 402.4 (37). SUBMIT TWO COPIES OF THE SPECIFIC
 SIZING TABLE FOR THE LOW PRESSURE SYSTEM.
 4) REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
 5) SHOW THE CAPACITY OF THE LP TANK ON THE PLANS AND
 SHOW THE TYPE OF TANK ( HORIZONTAL ASME OR VERTICAL
 ASME).
 6) SHOW THE TYPE OF FOUNDATION FOR THE LP TANK ON THE
 PLAN. HORIZONTAL ASME CONTAINERS SHALL COMPLY WITH NFPA
 58 SEC.6.6.3.1. VERTICAL ASME CONTAINERS SHALL COMPLY
 WITH NFPA 58-11 SEC. 6.6.4.1.
 7) SHOW THE DISTANCE OF THE LP TANK FROM THE EXTERIOR
 WALL OF THE STRUCTURE TO THE CONTAINER SURFACE AND ALSO
 FROM THE PROPERTY LINE TO THE CONTAINER SURFACE. COMPLY
 WITH NFPA 58-11 SEC. 6.3.1 & TABLE 6.3.1.
 8) THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 SHALL BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR
 SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
 9) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW