Date |
Text |
2017-07-10 08:50:53 | 1) THE SUBMITTED SHEET FOR THE LOCATION OF UNDERGROUND |
| LP TANK INSTALLATION IS FOR ILLUSTRATIVE PURPOSES ONLY. |
| THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY |
| WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF |
| THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE. |
| 2) A SHEET HAS BEEN SUBMITTED FOR THE UNDERGROUND TANK |
| INSTALLATION THAT REFERS TO A "3.2.9.1." WHAT STANDARD |
| IS THIS TAKEN FROM? THIS DOES NOT APPEAR TO BE FROM |
| NFPA 58 AND IS THEREFORE UNACCEPTABLE FOR PERMIT |
| PURPOSES. SUBMIT INFORMATION AS TO THE FOLLOWING: |
| A) SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY |
| WITH NFPA 58 SEC. 6.6.6.1. |
| B) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR |
| THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO |
| BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC. |
| 6.6.1.6. |
| C) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER |
| OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE, |
| 3) THE COPY OF THE TABLE 402.4 (34) IS FROM AN OUTDATED |
| FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS THE 2014 |
| FBC-FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT SIZING |
| TABLE. WPB AMEND. TO FBC SEC. 107.2.1. |
| 4) SUBMIT A COMPLETE COPY OF SIZING TABLE 15.1 (A) FROM |
| NFPA 58-11. THE SUBMITTED COPY HAS THE CORNER CUT OFF |
| AND THE PSI OF THIS TABLE CANNOT BE DETERMINED. THIS |
| TABLE IS NOT FROM THE 2011 EDITION. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE 402.4 |
| (28) FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| 6) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATION |
| SHEETS AND INSTALLATION INSTRUCTIONS FOR THE FISHER |
| REGULATORS. |
| 7) REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| 8) INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THEOUGH |
| THE EXTERIOR WILL BE PROTECTED.WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| |