Plan Review Notes
Plan Review Notes For Permit 17070147
Permit Number 17070147
Review Stop G
Sequence Number 1
Notes
Date Text
2017-07-10 08:50:531) THE SUBMITTED SHEET FOR THE LOCATION OF UNDERGROUND
 LP TANK INSTALLATION IS FOR ILLUSTRATIVE PURPOSES ONLY.
 THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY
 WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF
 THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE.
 2) A SHEET HAS BEEN SUBMITTED FOR THE UNDERGROUND TANK
 INSTALLATION THAT REFERS TO A "3.2.9.1." WHAT STANDARD
 IS THIS TAKEN FROM? THIS DOES NOT APPEAR TO BE FROM
 NFPA 58 AND IS THEREFORE UNACCEPTABLE FOR PERMIT
 PURPOSES. SUBMIT INFORMATION AS TO THE FOLLOWING:
 A) SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY
 WITH NFPA 58 SEC. 6.6.6.1.
 B) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
 C) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE,
 3) THE COPY OF THE TABLE 402.4 (34) IS FROM AN OUTDATED
 FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS THE 2014
 FBC-FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT SIZING
 TABLE. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT A COMPLETE COPY OF SIZING TABLE 15.1 (A) FROM
 NFPA 58-11. THE SUBMITTED COPY HAS THE CORNER CUT OFF
 AND THE PSI OF THIS TABLE CANNOT BE DETERMINED. THIS
 TABLE IS NOT FROM THE 2011 EDITION. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD.
 6) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATION
 SHEETS AND INSTALLATION INSTRUCTIONS FOR THE FISHER
 REGULATORS.
 7) REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
 8) INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THEOUGH
 THE EXTERIOR WILL BE PROTECTED.WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  