2018-02-14 09:26:18MECHANICAL PROVISOS
 THE BRISTOL
 REVISON #17070136
 2/14/2018
  
 THE MECHANICAL REVISION IS APPROVED WITH THE FOLLOWING
 LIST OF PROVISOS:
  
 1) PROVIDE THE BACK PRESSURE CALCULATIONS FOR THE
 GENERATOR EXHAUST PIPE, AND A REVISED DRAWING OF THE
 EXHAUST PIPE THAT SHOWS THE SEGMENTED LENGTHS OF THE
 PIPE AND THE TOTAL LENGTH OF THE RUN FROM THE GENERATOR
 TO THE OUTLET AT THE EXTERIOR WALL.
  
 2) PROVIDE ELECTRONICALLY SIGNED AND SEALED DRAWINGS
 AND DETAILS FOR THE FIRE-RATED EXHAUST PIPE ENCLOSURE.
  
 3) THE REVISED ENERGYGAUGE COMPLIANCE REPORT MUST BE
 ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO
 PREPARED THE CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  