Plan Review Notes For Permit 17070136 |
Permit Number |
17070136 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-02-14 09:26:18 | MECHANICAL PROVISOS | | THE BRISTOL | | REVISON #17070136 | | 2/14/2018 | | | | THE MECHANICAL REVISION IS APPROVED WITH THE FOLLOWING | | LIST OF PROVISOS: | | | | 1) PROVIDE THE BACK PRESSURE CALCULATIONS FOR THE | | GENERATOR EXHAUST PIPE, AND A REVISED DRAWING OF THE | | EXHAUST PIPE THAT SHOWS THE SEGMENTED LENGTHS OF THE | | PIPE AND THE TOTAL LENGTH OF THE RUN FROM THE GENERATOR | | TO THE OUTLET AT THE EXTERIOR WALL. | | | | 2) PROVIDE ELECTRONICALLY SIGNED AND SEALED DRAWINGS | | AND DETAILS FOR THE FIRE-RATED EXHAUST PIPE ENCLOSURE. | | | | 3) THE REVISED ENERGYGAUGE COMPLIANCE REPORT MUST BE | | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO | | PREPARED THE CALCULATIONS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|