2018-01-08 17:21:27 | 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #17070136 |
| 1/8/2018 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) IT IS ACKNOWLEDGED THAT THE USE OF FLAMEBAR DUCTWORK |
| TO REPLACE FIRE-RATED SHAFTS IN THE BUILDING HAS BEEN |
| GRANTED APPROVAL UNDER SECTION 104.11 FBC ALTERNATE |
| MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND |
| EQUIPMENT BY ROBERT BROWN WPB BUILDING OFFICIAL. THE |
| APPROVAL, HOWEVER, DOES NOT INCLUDE THE FLAMEBAR DUCTS, |
| OR ANY OTHER DUCTS, THAT ARE PENETRATING THE INTERIOR |
| EXIT STAIRWELL SHAFTS IN THE NORTH AND SOUTH CORES. |
| THIS CONDITION IS CURRENTLY BEING EVALUATED BY THE |
| BRISTOL DESIGN TEAM AND IS EXCLUDED FROM THIS REVIEW |
| UNTIL A LATER DATE. |
| |
| 2) COMMENT #2 FROM THE 1ST HAS NOT BEEN COMPLETELY |
| ADDRESSED. I AM UNABLE TO FIND THE SE-1 & SE-2 |
| IDENTIFICATION LABELS ON SHEETS M2.01, M2.02, & M2.03. |
| PLEASE SHOW THE LOCATIONS ON THE PLANS. |
| |
| 3) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. PER THE |
| RESPONSE NARRATIVE THE REQUESTED INFORMATION AND |
| SPECIFICATIONS FOR THE GENERATOR AND EXHAUST FLUE HAVE |
| BEEN PROVIDED, HOWEVER NO DOCUMENTS HAVE BEEN UPLOADED |
| FOR REVIEW. |
| |
| 4) COMMENT #4 FROM THE 1ST REVIEW HAS NOT BEEN COMPLETE |
| ADDRESSED. IT APPEARS THAT THE REVISED ENERGY |
| COMPLIANCE REPORT DOES NOT INCLUDE THE DATA FOR THE NEW |
| PARKING GARAGE HEAT PUMPS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |