Plan Review Notes For Permit 17070136 |
Permit Number |
17070136 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-01-12 14:10:07 | 2ND REVIEW COMMENTS | | | | | | 1) SHEET FP P 1 & P 2 - THERE APPEARS TO BE | | INSUFFICIENT FIRE SPRINKLER COVERAGE OVER THE NEW | | RESIDENT STORAGE AREAS. | | | | PROVISO: | | | | COMMENT PROVIDED - WILL REVIEW WITH SPRINKLER DRAWINGS | | AND INSPECTIONS. | | | | | | | | 2) SHEET FP 2.01 - THERE APPEARS TO BE NO FIRE | | SPRINKLER COVERAGE OVER THE WOOD DECK FLOORING AREA ON | | THE LOBBY SHEETS. | | | | PROVISO: | | | | COMMENT PROVIDED THAT PRODUCT SHEETS WILL BE PROVIDED - | | WILL REVIEW DRAWINGS, AMTERIALS AND INSPECTIONS. | | | | | | | | | | 3) SHEET 156 4A 13A - INDICATES THE WOOD DECKING WITH | | SUBFLOORING WITH A NOTE CALL-OUT "WOOD FINISH FLOOR, | | LANSCAPE DWG" BUT NO DRAWING REFERENCE SHEET. | | | | PROVISO: | | | | COMMENT PROVIDED THAT PRODUCT SHEETS WILL BE PROVIDED - | | WILL REVIEW DRAWINGS, AMTERIALS AND INSPECTIONS. | | | | | | | | | | 4) SHEETS FP P1 & P2 - THERE ARE INTERANL PRIVATE | | GARAGES INDICATED WITH THE PARKING GARAGE AREAS. THERE | | ARE NO INDICATIONS THAT WHEN THE INTERANL GARAGE DOOR | | IS OPEN, THAT FIRE SPRINKLER PROTECTION WILL BE | | PROVIDED FOR THE POSSIBLE OBSTRUCTION. | | | | | | PROVISO: | | | | COMMENT PROVIDED THAT PRODUCT SHEETS WILL BE PROVIDED - | | WILL REVIEW DRAWINGS, AMTERIALS AND INSPECTIONS. | | | | | | | | | | 5) FIRE SHARES IDENTICAL CONCERNS REGARDING THE FIRE | | DAMPERS, GENERATOR EXHAUST. SMOKE CONTROL SYSTEMS BUT | | WILL NOT BE DUPLICATED THOSE QUESTIONS. | | | | COMMENTS ARE BEING ADDRESSED THRU MECHANICAL | | | | | | | | 6) N/A | | | | | | 7) N/A | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|