2018-01-09 15:30:41 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17070136 |
| W. P. B. PERMIT: 15111020 |
| ADD: 1100 S. FLAGLER DR. |
| CONT: SUFFOLK CONSTRUCTION CO. |
| TEL: 561-832-1616 |
| E-MAIL: [email protected] / ED HANRATTY |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: TUES. JAN. 09 / 2018 |
| ACTION: DENIED |
| |
| 1) COMPLIED. |
| |
| 2) 2ND REQUEST. SUBMITTED FOR DIGITAL PLAN REVIEW IS |
| THE 2ND ELEVATION CERTIFICATE, BUILDING UNDER |
| CONSTRUCTION. PLEASE NOTE THE CERTIFICATE SUBMITTED |
| DATED 4/18/17 DOES SHOW A SIGNATURE AND SEAL BUT IT IS |
| NOT A DIGITAL SIGNATURE, IT APPEARS THIS WAS SCANNED IN |
| BUT ORIGINALLY A PAPER SCANNED TO BE ELECTRONIC BUT NO |
| ELECTRONIC SIGNATURE. EITHER SUBMIT AN ELECTRONIC |
| VERSION WITH ELECTRONIC SIGNATURE OR SUBMIT A PAPER |
| WITH ORIGINAL SEAL AND SIGNATURE. |
| SURVEYORS: F. S. 472.025 SEALS. . EACH REGISTRANT MAY |
| IN ADDITION REGISTER HIS OR HER SEAL ELECTRONICALLY IN |
| ACCORDANCE WITH SS. 668.001-668.006. DRAWINGS, PLANS, |
| SPECIFICATIONS, REPORTS, OR DOCUMENTS PREPARED OR |
| ISSUED BY A REGISTRANT MAY BE TRANSMITTED |
| ELECTRONICALLY AND MAY BE SIGNED BY THE REGISTRANT, |
| DATED, AND STAMPED ELECTRONICALLY WITH SUCH SEAL IN |
| ACCORDANCE WITH SS. 668.001-668.006. |
| |
| LINE A4 INDICATES THIS TO BE A RESIDENTIAL BUILDING. |
| PLEASE NOTE USING THE FEMA DEFINITIONS, THIS IS NOT A |
| RESIDENTIAL BUILDING, BUT A MIXED USE BUILDING. |
| |
| LINE C2A) THE TOP OF THE BOTTOM FLOOR INCLUDING |
| BASEMENT IS INDICATED AS 11.00 FEET NGVD. NO THE BOTTOM |
| PARKING FLOOR IS LOWER ELEVATION THAN INDICATED. THE |
| BOTTOM OF THE BUILDING IS DRY FLOOD PROOFED, BFE + 1 |
| FOOT. |
| |
| LINE C2D) INDICATES THE LOWEST SLAB AT 0.30 FT. NGVD IS |
| THIS THE ELEVATOR PIT? |
| |
| LINE C2E) LOWEST ELEVATION OF MACHINERY OR EQUIPMENT |
| SERVING THE BUILDING. PLEASE NOTE THERE IS ELECTRICAL |
| SWITCH GEAR BELOW THE BFE BUT THE BUILDING IS DRY FLOOD |
| PROOFED. THIS BUILDING IS BUILT TO FEMA'S TECHNICAL |
| BULLITIN 3-93. FLOODPROOFED MIXED USE BUILDINGS THAT |
| ARE PROFESSIONALLY DESIGNED WITH ALL RESIDENTIAL USES |
| LOCATED ABOVE THE FLOODPROOFING DESIGN ELEVATION. |
| DESIGNED TO RESIST THE HYDROSTATIC FLOOD FORCES AND A |
| FLOOD EMERGENCY OPERATION PLAN. |
| |
| |
| 3A) BUILDING PROVISO: COMMENT AS TO SHEET 102-A2.52B |
| AND SHEET 156-A4.13A DETAIL # 5. THE PLANS SHOW DOUBLE |
| WOOD SLEEPERS AND WOOD DECK. THE PLANS ARE SILENT AS TO |
| THE TYPE OF WOOD THE SLEEPERS AND DECK WILL BE MADE. |
| HOW THE DECK WILL BE ANCHORED IN HIGH WIND EVENTS. |
| SPACING OF THE SLEEPERS, THICKNESS OF DECK MATERIALS, |
| SPACING OF MATERIAL AND THE COMPLIANCE WITH 2010 FBC-B |
| 603.1.1 FIRE RETARDANT TREATED WOODS. |
| |
| 3B-C) COMPLIED. |
| |
| 4A) COMPLIED. THE BUILDING OFFICIAL ROBERT BROWN HAS |
| APPROVED THE USE OF FLAME BAR UNDER 104.11.1 ALTERNATE |
| MATERIALS AND METHODS OF CONSTRUCTION FOR THE REPLACING |
| SHAFT CONSTRUCTION WITH THE EXCEPTION OF WHERE THE |
| PLANS SHOW DROPPED CEILINGS IN THE STAIRWELL LANDINGS. |
| THIS CONDITION WILL NOT BE PART OF THIS APPROVAL AS |
| DISCUSSED IN THE LAST MEETING AND WILL BE FURTHER |
| APPROVAL AND EVALUATION BY THE BRISTOL TEAM AND TO BE |
| REVIEWED BY THE BUILDING OFFICIAL ROBERT BROWN. |
| |
| 4B) PROVISO: SHAFT WALLS AND CHASE WALLS TO COMPLY WITH |
| 2010 FBC-B 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS |
| AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS |
| FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL |
| HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED |
| IN ACCORDANCE WITH ASTM E 90. |
| |
| 5) PROVISO: RESPONSE INDICATES THE ROOFING COMPOSITION |
| IS STILL PENDING TO BE PROVIDED AT A LATER TIME AS A |
| DEFERRED SUBMITTAL. 107.3.4.2. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 6) COMPLIED. STRUCTURAL WALL DETAILS OF POOL, HOT TUB |
| AND SPAS ARE TO BE SUBMITTED UNDER THE POOL PERMITS |
| 17100628 MAIN POOL & HOT TUB |
| 17100632 MENS JACUZZI |
| 17100635 WOMENS JACUZZI |
| 17100637 SPLASH PAD |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |