Plan Review Notes
Plan Review Notes For Permit 17070136
Permit Number 17070136
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-03 10:17:391ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P2-0P1, P2-0P2, P2-01, P2-02, AND P2-03 PLEASE
 LABEL ALL STACKS TO MATCH UP WITH ISO DRAWINGS, TO
 INCLUDE WATER SANITARY AND GAS. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT. P5-03C, D, E, AND P5-23 PLEASE SHOW THE LEVELS
 ON ISOMETRIC DRAWINGS, AND INDICATE LOCATION ON THE
 ISO. PER WPB AMEND TO FBC 107.2.1
  
 3. PLEASE SHOW COMPLIANCE IN ALL BATHROOMS IN COMMON
 AREAS WITH FBC ACC
 A) 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 B) 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 C) 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES
 (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT
 BE LOCATED BEHIND GRAB BARS
 D) 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 E) 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 F) 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 G) 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4. PLEASE SHOW COMPLIANCE IN NEW COMMON BATHROOMS WITH
 FBC ACC
  
 A) 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 B) 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 C) LAVATORIES 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5. PLEASE REMOVE OLD REVISION CLOUDS FROM ALL SHEETS IT
 HAS BEEN VERY DIFFICULT TO LOCATE THE CHANGES ON THIS
 REVISION, HERE IS A LIST OF PLAN PAGES THAT I COULD NOT
 SEE ANY CHANGES FROM THE APPROVED PLAN PAGE: P2.19,
 P1.25, P2.26, P2.53A, P2.54A, P2.54C, P2.54G, P2.56B,
 P2.57B, P5.01, P5.02, P5.03, P5.03B. PER WPB AMEND TO
 FBC 107.2.1
  
 6. AAV ARE NOT PERMITTED BELOW 4TH BRANCH DOWN FROM
 ROOF NOT STILL ON FLOOR PLANS PLEASE REMOVE SHT.
 P2.55A, P2.55C PLEASE CHECK ALL FLOOR PLAN SHEETS. PER
 FBC PL 918.3.1/ WPB AMEND TO FBC 107.2.1
  
 7. SHT. P5.23 IS MISSING ISO #2 FROM APPROVED PLAN
 SHEET. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P5.03C PLEASE PROVIDE ISO THAT SHOWS SS S7, S8,
 AND S9 CONNECTING TO ONE SINGLE STACK AND SHOW THE
 LEVEL. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. P2.01 THE SOIL STACK ON THE BACK SIDE OF
 ELEVATOR #1 SHOWS A 4? PIPE SHT. P2.0P1 SHOWS A 6? AT
 SAME LOCATION PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 10. ON THE RISER AND ISO DRAWINGS THERE ARE VENTS THAT
 END AND IT IS NOT CLEAR WHERE THEY CONTINUE OR
 TERMINATE PLEASE PROVIDE A TAG OR A WAY OF DETERMINING
 WHERE THEY CONTINUE OR TERMINATE. PER WPB AMEND TO FBC
 107.2.1
  
 11. SHT. P5.03B S12 LEVEL 25 THE ISO DOES NOT MATCH THE
 FLOOR PLAN ON SHT. P2.61B PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 12. PROVIDE ISO FOR NEW BATHROOMS ON LEVEL 1. PER WPB
 AMEND TO FBC 107.2.1
  
 13. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 LAUNDRY TRENCH DRAIN. PER WPB AMEND TO FBC 107.2.1
  
 14. PLEASE PROVIDE A REVISED CONDENSATE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
  
 POOL COMMENTS :
  
 1. SHT. W1-1.02 THE NOTE ON GUTTER DRAIN SHOULD BE 20
 WITH THE ADDITIONAL DRAIN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 2. SHT. W1-2.02 SHOW THE PIPE SIZE FOR THE NEW FLOOR
 HYDROTHERAPY JETS ALSO CHECK THE HIS AND HERS SPAS FOR
 PIPE SIZES. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE CHLORINE
 GENERATOR AND SACRIFICIAL ANODE AND STEAM UNIT. PER WPB
 AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE PIPING DIAGRAM AND DETAILS FOR STEAM
 SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. W1-2.01, W1-4.01, W1-5.01, W5-1.05 THE REVISED
 PAGES APPEAR TO BE THE SAME AS APPROVED PAGES PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  