Plan Review Notes For Permit 17070109
Permit Number 17070109
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-07 15:06:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE WAS NO MANUFACTURES SPECIFICATION SHEETS FOR
 THE FLOORING OR UNDERLAYMENT PROVIDED WITH THIS
 SUBMITAL THAT SHOWS COMPLIANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 PER NFPA 101, CHAPTER 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS CORRIDORS AND SPACES NOT SEPARATED FROM
 THEM BY WALLS COMPLYING WITH 30.3.6 SHALL BE NOT LESS
 THAN CLASS II.
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR 10.2.7.2, AS APPLICABLE.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE,
 SHALL HAVE A MINIMUM CRITICAL RADIANT FLUX OF 0.1
 W/CM2.
 10.2.7.3* INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH 10.2.7.4, BASED ON TEST RESULTS FROM
 NFPA 253, STANDARD METHOD OF TEST FOR CRITICAL RADIANT
 FLUX OF FLOOR COVERING SYSTEMS USING A RADIANT HEAT
 ENERGY SOURCE, OR ASTM E 648, STANDARD TEST METHOD FOR
 CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS USING A
 RADIANT HEAT ENERGY SOURCE.
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED AS
 FOLLOWS IN ACCORDANCE WITH THEIR CRITICAL RADIANT FLUX
 VALUES:
 (1) CLASS I INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
 (2) CLASS II INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.22 W/CM2 BUT LESS THAN 0.45 W/CM2, AS DETERMINED BY
 THE TEST DESCRIBED IN 10.2.7.3.
  
  
 PLEASE PROVIDE THE SPECIFICATION SHEETS THAT INDICATE
 COMPLIANCE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  