2017-07-11 09:45:08 | 1) THE COPY OF SIZING TABLE 15.1 ( B) IS ILLEGIBLE. |
| SUBMIT A CLEAR AND LEGIBLE COPY FOR REVIEW. WPB AMEND. |
| TO FBC SEC. 107.2.1. |
| 2) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR |
| OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. THE NOTE " |
| "GAS CODES BASED ON 402.4 SERIES FBC CODES" IS VAGUE. |
| CLARIFY. |
| 3) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| G2413.3. |
| 4) SUBMIT A CLEAR AND LEGIBLE SURVEY FOR REVIEW THAT |
| CLEARLY SHOWS THE LOCATION OF THE EXISTING PROPANE |
| TANK, METER, AND THE LOCATION OF THE NEW GENERATOR. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 5)SUBMIT TWO COPIES OF THE SPECIFIC SIZING TABLE FOR |
| THE LOW PRESSURE SYSTEM. |
| 6) SHOW THE CAPACITY OF THE LP TANK ON THE PLANS AND |
| SHOW THE TYPE OF TANK ( HORIZONTAL ASME OR VERTICAL |
| ASME). |
| 7) SHOW THE TYPE OF FOUNDATION FOR THE LP TANK ON THE |
| PLAN. HORIZONTAL ASME CONTAINERS SHALL COMPLY WITH NFPA |
| 58 SEC.6.6.3.1. VERTICAL ASME CONTAINERS SHALL COMPLY |
| WITH NFPA 58-11 SEC. 6.6.4.1. |
| 8) SHOW THE DISTANCE OF THE LP TANK FROM THE EXTERIOR |
| WALL OF THE STRUCTURE TO THE CONTAINER SURFACE AND ALSO |
| FROM THE PROPERTY LINE TO THE CONTAINER SURFACE. COMPLY |
| WITH NFPA 58-11 SEC. 6.3.1 & TABLE 6.3.1. |
| 9) THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| SHALL BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR |
| SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE |
| GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. |
| 10) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| G2413.3. |
| |