Plan Review Notes
Plan Review Notes For Permit 17070088
Permit Number 17070088
Review Stop E
Sequence Number 2
Notes
Date Text
2017-09-22 07:15:53PERMIT APPROVED WITH EXCEPTION. THE FOLLOWING ITEMS
 NEED TO BE CORRECTED AND RE-SUBMITTED BEFORE FIRST
 INSPECTION:
  
 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE INTERSYSTEM
 BONDING TERMINATION POINT REQUIRED. PROVIDE CORRECTION.
 NEC 250.94; FBC RE3609.3
 2. RESPONSE TO COMMENTS STATES THAT 4 CIRCUIT ARE USED
 FOR THE DETACHED BUILDING, WHICH IS A CODE VIOLATION.
 CODE STATES: "A BUILDING OR OTHER STRUCTURE THAT IS
 SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE
 OF A SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY
 ONLY ONE FEEDER OR BRANCH CIRCUIT". PROVIDE CORRECTION.
 NEC 225.30
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  