2017-09-05 17:22:15 | RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED INFORMATION |
| AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO |
| AVOID CONFLICTS/DELAYS. FEES MAY APPLY. CONTRACTOR TO |
| ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME. |
| CONTRACTOR TO SUBMIT SEPARATE PERMIT APPLICATION FOR |
| THE GARAGE STRUCTURE BEFORE ISSUING ANY PERMITS. |
| |
| 1- THERE ARE TWO SEPARATE STRUCTURES IN THIS PROPERTY. |
| NEED A SEPARATE PERMIT APPLICATIONS FOR EACH STRUCTURE. |
| ONE PERMIT APPLICATION FOR THE MAIN HOUSE AND THE OTHER |
| ONE FOR THE GARAGE CONVERSION TO LIVABLE SPACE. SEC. |
| 105.1 CITY AMENDMENTS. |
| NOTE: THERE ARE NOT ADDITIONAL FEES FOR THE REAR |
| STRUCTURE PERMIT APPLICATIONS. FEES ARE ALREADY |
| INCLUDED IN THE OVERALL SCOPE OF WORK IN THE ORIGINAL |
| PERMIT APPLICATION. SEPARATE PERMIT APPLICATIONS ARE TO |
| FACILITATE AND COORDINATE ALL THE INSPECTIONS AND FOR |
| PROPER RECORD RETENTION FILES. CONTRACTOR MAY USE SAME |
| PLANS FOR BOTH STRUCTURES. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- PROPOSED CABANA ON THE EXISTING GARAGE: SHOW |
| COMPLIANCE WITH THE HEATING REQUIREMENTS OF SEC. R303.9 |
| FBC-RESIDENTIAL. NOTE: PORTABLE UNITS ARE NOT ALLOWED. |
| RESPONSE: INFORMATION ON THE TOP LEFT HAND SIDE AND |
| CABANA FLOOR PLAN ON SHEET E-1 SHOW AN EXISTING A/C |
| UNIT TO BE RELOCATED ABOVE THE DOUBLE FRENCH DOORS. |
| PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE |
| RELOCATED A/C UNIT IS GOING TO BE INSTALLED ABOVE THE |
| NEW FRENCH DOORS. IT DOESN'T SEEM TO BE ENOUGH ROOM. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| HANDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF |
| TABLE R301.5 AND SPECIFICATIONS OF SEC. R311.7.8 AND |
| SEC. R312.1 FBC-RESIDENTIAL. SPECIFY MATERIAL, |
| FASTENERS, HEIGHT, PICKETS SPACING, ETC. |
| RESPONSE: THE HANDRAILS WERE REMOVED. HANDRAILS CAN NOT |
| BE REMOVED. SEE SECTION R311.7.8 FBC-RESIDENTIAL. |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS AS REQUIRED |
| ON THE ORIGINAL COMMENT. |
| |
| PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |