2017-07-25 07:41:41CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 THE SIGNATURE ON THE PLAN DOES NOT APPEAR TO BE FROM A
 LICENSED ENGINEER OR ARCHITECT. FS 471.003(2)(H);
 471.025; FBC 107.2.1
 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC
 210.70(A)(2)(B), FBC RE3903.3
 3. PROVIDE PANEL SCHEDULE ON PLAN INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
 FBC RE3706.2, RE3902
 4. NOTE 19 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PROVIDE ACCURATE LOAD CALCULATION ON PLAN INCLUDING
 ALL LOADS. NEC 220; FBC RE3602.3; FBC 107.2.1
 8. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR POOL AND ALL LOW VOLTAGE SYSTEMS TO
 INCLUDE BUT NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND
 DATA, WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL
 SUFFICE. FBC 105.1
 9. THE CIRCUITRY TO THE GARAGE BUILDING IS NOT SHOWN.
 PER CODE: "A BUILDING OR OTHER STRUCTURE THAT IS SERVED
 BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A
 SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY
 ONE FEEDER OR BRANCH CIRCUIT. NEC 225.30" SHOW CIRCUIT
 AND/OR CIRCUITS TO GARAGE, CORRECT IF NECESSARY. NEC
 225.30
 10. BATHROOM GFCI OUTLETS ARE REQUIRED TO BE ON A
 DEDICATED 20 AMP CIRCUIT. SHOW CIRCUIT ON PLANS. FBC
 107.2.1; NEC 210.11(C)(3) , FBC RE3703.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  