Plan Review Notes
Plan Review Notes For Permit 17070088
Permit Number 17070088
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-01 12:56:59RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THERE ARE TWO SEPARATE STRUCTURES IN THIS PROPERTY.
 NEED A SEPARATE PERMIT APPLICATIONS FOR EACH STRUCTURE.
 ONE PERMIT APPLICATION FOR THE MAIN HOUSE AND THE OTHER
 ONE FOR THE GARAGE CONVERSION TO LIVABLE SPACE. SEC.
 105.1 CITY AMENDMENTS.
 NOTE: THERE ARE NOT ADDITIONAL FEES FOR THE REAR
 STRUCTURE PERMIT APPLICATIONS. FEES ARE ALREADY
 INCLUDED IN THE OVERALL SCOPE OF WORK IN THE ORIGINAL
 PERMIT APPLICATION. SEPARATE PERMIT APPLICATIONS ARE TO
 FACILITATE AND COORDINATE ALL THE INSPECTIONS AND FOR
 PROPER RECORD RETENTION FILES. CONTRACTOR MAY USE SAME
 PLANS FOR BOTH STRUCTURES.
  
 3- SPECIFY THE DESIGN PRESSURES FOR ALL DOORS AND
 WINDOWS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 NOTE: PRODUCT APPROVALS WILL BE REVIEWED ONCE THE
 CALCULATED DESIGN PRESSURES ARE PROVIDED.
  
 4- PROPOSED CABANA ON THE EXISTING GARAGE: SHOW
 COMPLIANCE WITH THE HEATING REQUIREMENTS OF SEC. R303.9
 FBC-RESIDENTIAL. NOTE: PORTABLE UNITS ARE NOT ALLOWED.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 HANDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF
 TABLE R301.5 AND SPECIFICATIONS OF SEC. R311.7.8 AND
 SEC. R312.1 FBC-RESIDENTIAL. SPECIFY MATERIAL,
 FASTENERS, HEIGHT, PICKETS SPACING, ETC.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 RISERS AND TREADS SHOWN COMPLIANCE WITH SEC. 311.7.5
 FBC-RESIDENTIAL. SPECIFY RISER HEIGHT, NOSING, ETC.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) STORAGE SINGLE FIBERGLASS DOOR AS SHOWN ON PLANS.
 FLORIDA PRODUCT APPROVAL FL17184.12 SUBMITTED IS FOR
 DOOR WITH SIDE-LITE ASSEMBLY. IT DOESN'T MATCH PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER OF RECORD TO LIST THE CURRENT
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 8- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS BEFORE SUBMITTAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 9- CLEARLY SPECIFY SIZE OF MULLIONS TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
  
 10- SPRAY INSULATION ICC EVALUATION REPORT ESL-1060
 SUBMITTED:
 A) PROVIDE CURRENT REPORT. THE ONE SUBMITTED EXPIRED ON
 03/2017. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) PLANS DON'T SHOW ANY SPRAY INSULATION. ENGINEER OF
 RECORD TO CLEARLY SPECIFY ON PLANS AND WALL
 SECTIONS/DETAILS INSULATION TYPE AND LOCATION. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) ENGINEER OF RECORD TO REVIEW AND APPROVE INSULATION
 REPORT PRIOR TO SUBMITTAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]