2017-07-14 15:25:36 | FAILED | | | | PROVIDE WRITTEN RESPONSE. | | | | 1) THE FONT FOR THE FOOTCANDLES IS NOT LARGE ENOUGH TO | | READ. PLEASE PROVIDE THE NUMBERS IN A LARGER FONT. | | | | 2) THE ZONING AND LAND DEVELOPMENT CODE REQUIRES THAT | | THE MAXIMUM FOOTCANDLE AT THE PROPERTY LINE IS 1.0. THE | | CALCULATION SUMMARY LISTS THE MAXIMUM FOOTCANDLES AS | | HIGH AS 50.8 ON THE SOUTH PROPERTY LINE. PLEASE RECHECK | | THE FOOTCANDLES AT THE PROPERTY LINES TO CONFORM WITH | | THE ZONING AND LAND DEVELOPMENT REGULATIONS. | | | | 3) THE LIGHT LOCATIONS SHOWN ON THE LIGHTING SITE PLAN | | DO NOT MATCH THE LOCATIONS SHOWN ON THE SITE AND | | LANDSCAPE PLANS. ALL PLANS SHALL SHOW THE SAME | | CONDITIONS. PLEASE NOTE THAT THE LIGHT POLES MAY NOT | | INTERFERE WITH TREE LOCATIONS. | | | | 4) PROVIDE VERIFICATION THAT THE LIGHT POLES ALONG THE | | ROADWAYS DO NOT CREATE GLARE INTO THE ADJACENT | | RIGHTS-OF-WAY. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | ESCHNEIDER@ WPB.ORG | 2017-07-06 14:28:54 | ROUTED TO ERIC SCHNEIDER |
|