2017-07-12 12:35:31CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN REQUIRED TO BE SIGNED AND SEALED BY
 DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5
 2. SHOW COMPLIANCE WITH ENERGY CODE FOR LIGHTING: "A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1
 3. PROVIDE CORRECTED PANEL SCHEDULE. CIRCUIT 22 SHOWS
 AS A SMALL APPLIANCE CIRCUIT, BUT IT IS FEEDING OUTDOOR
 OUTLETS. CIRCUITS 24, 26, AND 30 SHOULD BE AFCI
 PROTECTED CIRCUITS. CIRCUIT 9,11 FOR WATER HEATER
 SHOULD BE A 25 AMP BREAKER. NEC 215.5, 408.4, 408.30,
 422.13; FBC 107.2.1, FBC RE3706.1
 4. WIRE FEEDING INTERIOR PANEL FROM OUTSIDE SERVICE IS
 TOO SMALL. 2/0 COPPER CAN ONLY BE USED WHERE IT FEEDS
 100% OF THE LOAD. PROVIDE CORRECTION. NEC 310.15(B)(7);
 FBC RE3602.2
 5. LIGHT IN MASTER CLOSET IS SHOWN AS BEING ON THE SAME
 CIRCUIT AS THE BATHROOM GFCI OUTLETS, WHICH IS NOT
 PERMITTED PER CODE. PROVIDE CORRECTION. NEC
 210.11(C)(3); FBC RE3703.4
 6. KITCHEN COUNTER OUTLETS SHOW ONLY ONE CIRCUIT (#20).
 CODE REQUIRES MINIMUM OF 2 SMALL APPLIANCE CIRCUITS.
 PROVIDE CORRECTION. NEC 210.11(C)(1), 210.52(B)(2); FBC
 RE3703.2
 7. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE
 CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER
 CODE. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B)(2); FBC RE3703.2
 8. BATH 2 LIGHT OVER SHOWER SHOWS A STANDARD LIGHT. PER
 CODE: "LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS". PROVIDE CORRECTION OR
 NOTE TO COMPLY. NEC 410.10(D); FBC RE4003.11
 9. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". LIGHT IN MASTER
 CLOSET IS NOT SPECIFIED. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 10. IN SEVERAL LOCATIONS THE OUTLET SPACING IS NOT
 WITHIN THE LIMITS PER CODE: "RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET". PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER