Plan Review Notes
Plan Review Notes For Permit 17070011
Permit Number 17070011
Review Stop B
Sequence Number 3
Notes
Date Text
2017-08-11 15:38:273RD REVIEW FBC-2014 BUILDING
 PERMIT #17070011
 8/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE TAMKO NOA WAS RESUBMITTED A THIRD TIME WITHOUT
 THE REQUIRED ENGINEERING FOR THE FLAT ROOF- SEE 1ST
 REVIEW COMMENT PRINTED BELOW.
  
 2) REFER TO LIMITATION #7 ON PAGE 15 OF NOA #
 17-0222.09: INCREASED FASTENER DENSITIES AT PERIMETER
 AND CORNER AREAS REQUIRED. PROVIDE CALCULATIONS
 PREPARED AND SIGNED AND SEALED BY A FL. REGISTERED
 PROFESSIONAL ENGINEER, ARCHITECT, OR REGISTERED ROOF
 CONSULTANT.
  
 3) THE PERMIT VALUE OF $1560.00 FOR THE POPOSED ROOF
 REPLACEMENT APPEARS TO BE LOW. IN ACCORDANCE WITH
 SECTION 109.3 WPB AMENDMENTS TO THE FBC, PLEASE
 INDICATE THE SQUARE FOOTAGE AREAS OF THE FLAT ROOF AND
 SHINGLE ROOFS ON THE PERMIT APPLICATION AND SUBMIT A
 SIGNED CONTRACT.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  