2017-06-30 15:06:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT IS UNCLEAR ON THE SUBMITTED PLAN, IS FARMER &
 IRWIN THE ENGINEER OF RECORD, IF SO THERE IS NO
 INDICATIORS PER 61G15-32.003 COMMON REQUIREMENTS TO ALL
 FIRE PROTECTION ENGINEERING DOCUMENTS & 61G15-32.004
 DESIGN OF WATER BASED FIRE PROTECTION SYSTEMS.
  
 PLEASE CORRECT OR CLARIFY IF A STAMP OR SEAL OR
 APPROVAL OF THE EOR IS REQUIRED.
  
  
  
 2) IT IS NOT CLEAR WHERE THE INSTALLATION STARTS AND OR
 STOPS. THE PLAN ARE TOO SMALL TO CLEARLY IDENTIFFY,
  
 PLEASE CORRECT.
  
  
  
 3) THERE WERE NO MANUFACTURES SPECIFICATION/INSTALLTION
 SHEETS PROVIDED.
  
 PLEASE PROVIDE THEM.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  