2017-10-19 10:47:57 | 2ND REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS8US COMMENTS HAVE NOT BEEN |
| COMPLIED WITH. |
| |
| 2ND REQUEST1. THE WASHING MACHINES ON FIRST AND SECOND |
| FLOOR ARE MISSING FROM RISER DIAGRAMS WATER AND |
| SANITARY PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.3.5.3(11) |
| |
| 2ND REQUEST 2. SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 |
| SHOW AN ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES |
| IF NOT GAS |
| |
| 2ND REQUEST 3. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 |
| SHOW AN ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES |
| IF NOT GAS |
| |
| 2ND REQUEST 4. SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF |
| THE AC UNITS ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS |
| WH NORTH OF AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE |
| EAST WALL P1 SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS |
| ON THE EAST WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |