Date |
Text |
2017-10-19 10:50:19 | 2ND REVIEW: FBC 2014 5TH EDITION |
| |
| GAS COMMENTS: PLEASE REMOVE REFERENCE TO GAS APPLIANCES |
| IF NOT GAS |
| |
| 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 PLEASE |
| REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS |
| |
| 2. SHOW LOCATION OF TANKLESS WATER HEATERS ON ELEVATION |
| PLAN SHT. IN COMPLIANCE OF MANUFACTURE INSTALLATION |
| GUIDE 4FT FROM OPERABLE WINDOW. PER WPB AMEND TO FBC |
| 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF |
| NOT GAS |
| |
| 3.SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 SHOW AN |
| ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF |
| NOT GAS |
| |
| 4. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 SHOW AN |
| ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF |
| NOT GAS |
| |
| 5.SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF THE AC UNITS |
| ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS WH NORTH OF |
| AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE EAST WALL P1 |
| SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS ON THE EAST |
| WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1 PLEASE |
| REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |