2017-10-25 13:44:35CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS: PREVIOUS COMMENTS CORRECTED
 ARE NOTED AS CORRECTED. COMMENTS THAT NEED FURTHER
 CORRECTION HAVE ADDITIONAL INFORMATION IN PARENTHESES.
  
 1. PLAN SHOWS 2 SERVICES, WHICH IS NOT PERMITTED PER
 CODE. REVISE TO SHOW ONE SERVICE WITH 2 METERS. PROVIDE
 NEW RISER DIAGRAM TO MATCH. PROVIDE LOAD CALCULATION
 FOR ENTIRE SERVICE, PROVIDE ADEQUATE SIZE CONDUCTOR IN
 SERVICE RISER TO ACCOMMODATE LOAD, AND PROPERLY SIZED
 GROUNDING ELECTRODE SYSTEM. NEC 230.2, 215.5, 220,
 250.50; FBC RE3601.2, 3602.1, 3608.1 (LOAD CALCULATION
 PROVIDED IS FOR A MULTI-FAMILY DWELLING WITH 3 UNITS,
 WHICH DOES NOT APPLY WHEN THERE ARE ONLY 2 UNITS. THE
 DEMAND FACTOR APPLIED IS NOT PERMITTED FOR THIS. IT
 APPEARS THAT THE 3/0 WIRE STATED FOR THE SERVICE RISER
 IS OF ADEQUATE SIZE, BUT THE LOAD CALCULATION NEEDS TO
 BE ACCURATE.)
 2. CORRECTED
 3. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE
 "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING
 IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE
 REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF
 THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 406.12; FBC RE4002.14 (NOTE 4 HAS BEEN
 EDITED, BUT IT STILL STATES THE WRONG CODE REFERENCE.
 IT SHOULD BE EITHER NEC 406.12 OR FBC RE 4002.14)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  