2017-10-25 13:44:35 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: PREVIOUS COMMENTS CORRECTED |
| ARE NOTED AS CORRECTED. COMMENTS THAT NEED FURTHER |
| CORRECTION HAVE ADDITIONAL INFORMATION IN PARENTHESES. |
| |
| 1. PLAN SHOWS 2 SERVICES, WHICH IS NOT PERMITTED PER |
| CODE. REVISE TO SHOW ONE SERVICE WITH 2 METERS. PROVIDE |
| NEW RISER DIAGRAM TO MATCH. PROVIDE LOAD CALCULATION |
| FOR ENTIRE SERVICE, PROVIDE ADEQUATE SIZE CONDUCTOR IN |
| SERVICE RISER TO ACCOMMODATE LOAD, AND PROPERLY SIZED |
| GROUNDING ELECTRODE SYSTEM. NEC 230.2, 215.5, 220, |
| 250.50; FBC RE3601.2, 3602.1, 3608.1 (LOAD CALCULATION |
| PROVIDED IS FOR A MULTI-FAMILY DWELLING WITH 3 UNITS, |
| WHICH DOES NOT APPLY WHEN THERE ARE ONLY 2 UNITS. THE |
| DEMAND FACTOR APPLIED IS NOT PERMITTED FOR THIS. IT |
| APPEARS THAT THE 3/0 WIRE STATED FOR THE SERVICE RISER |
| IS OF ADEQUATE SIZE, BUT THE LOAD CALCULATION NEEDS TO |
| BE ACCURATE.) |
| 2. CORRECTED |
| 3. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE |
| "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING |
| IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE |
| REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF |
| THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR |
| CORRECTION. NEC 406.12; FBC RE4002.14 (NOTE 4 HAS BEEN |
| EDITED, BUT IT STILL STATES THE WRONG CODE REFERENCE. |
| IT SHOULD BE EITHER NEC 406.12 OR FBC RE 4002.14) |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. CORRECTED. |
| 9. CORRECTED. |
| 10. CORRECTED. |
| 11. CORRECTED. |
| 12. CORRECTED. |
| 13. CORRECTED. |
| 14. CORRECTED. |
| 15. CORRECTED. |
| 16. CORRECTED. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |