2017-07-18 15:41:26 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | 2. SHOW LOCATION OF TANKLESS WATER HEATERS ON ELEVATION | | PLAN SHT. IN COMPLIANCE OF MANUFACTURE INSTALLATION | | GUIDE 4FT FROM OPERABLE WINDOW. PER WPB AMEND TO FBC | | 107.2.1 | | | | 3.SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 SHOW AN | | ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 4. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 SHOW AN | | ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 5.SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF THE AC UNITS | | ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS WH NORTH OF | | AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE EAST WALL P1 | | SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS ON THE EAST | | WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|