2017-07-18 10:36:51 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PLAN SHOWS 2 SERVICES, WHICH IS NOT PERMITTED PER |
| CODE. REVISE TO SHOW ONE SERVICE WITH 2 METERS. PROVIDE |
| NEW RISER DIAGRAM TO MATCH. PROVIDE LOAD CALCULATION |
| FOR ENTIRE SERVICE, PROVIDE ADEQUATE SIZE CONDUCTOR IN |
| SERVICE RISER TO ACCOMMODATE LOAD, AND PROPERLY SIZED |
| GROUNDING ELECTRODE SYSTEM. NEC 230.2, 215.5, 220, |
| 250.50; FBC RE3601.2, 3602.1, 3608.1 |
| 2. LOAD CALCULATION PROVIDED FOR EACH UNIT DOES NOT |
| INCLUDE THE RANGE. PROVIDE CORRECTION TO INCLUDE THE |
| RANGE. NEC 210.19(3), 220.55; FBC RE3602.2, 3702.9.1 |
| 3. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE |
| "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING |
| IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE |
| REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF |
| THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR |
| CORRECTION. NEC 406.12; FBC RE4002.14 |
| 3. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE |
| AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE |
| ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT |
| DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS |
| REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE |
| CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12 |
| 4. UNIT B SHOW THE BATHROOM OUTLETS ON A 15 AMP |
| CIRCUIT, AND IT DOES NOT SHOW A GFCI OUTLET LOCATED |
| WITHIN 3 FEET OF THE BASIN. PROVIDE 20 AMP CIRCUIT AND |
| OUTLET PER CODE. NEC 210.11(C)(3) , 210.52(D) FBC |
| RE3703.4, 3901.6 |
| 5. UNIT B, CIRCUIT 19,21 SHOWS THE AHU ON A 45 AMP |
| BREAKER. SPECS FROM MECHANICAL DRAWING SHOW A MAX 30 |
| AMP BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC |
| RE3702.11 |
| 6. UNIT B, CIRCUIT 16,18 SHOW A 20 AMP CIRCUIT TO THE |
| RANGE. A MINIMUM 40 AMP CIRCUIT IS REQUIRED. PROVIDE |
| CORRECTION. NEC 210.19(3), 220.55; FBC RE3602.2, |
| 3702.9.1 |
| 7. UNIT B SHOWS THE DINING ROOM LIGHT ON THE SAME |
| CIRCUIT AS THE DINING ROOM OUTLETS, WHICH IS NOT |
| PERMITTED PER CODE. PROVIDE CORRECTION. NEC |
| 210.11(C)(1), 210.52(B)(2); FBC RE3703.2 |
| 8. UNIT B AND C SHOW ONLY ONE SMALL APPLIANCE CIRCUIT |
| FEEDING THE KITCHEN COUNTER OUTLETS. CODE REQUIRES A |
| MINIMUM OF 2 CIRCUITS. PROVIDE CORRECTION. NEC |
| 210.11(C)(1), 210.52(B)(3); FBC RE3703.2 |
| 9. UNIT C, CIRCUIT 18, SHOWS THE BATHROOM OUTLETS ON A |
| 15 AMP CIRCUIT, WHICH IS NOT PERMITTED PER CODE. |
| PROVIDE CORRECTION. NEC 210.11(C)(3); FBC RE3703.4, |
| 3901.6 |
| 10. UNIT C, CIRCUIT 17,19 SHOWS THE AHU ON A 45 AMP |
| BREAKER. SPECS FROM MECHANICAL DRAWING SHOW A MAX 30 |
| AMP BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC |
| RE3702.11 |
| 11. UNIT C SHOWS THE DINING ROOM ON A 15 AMP CIRCUIT, |
| WHICH IS NOT PERMITTED PER CODE. PROVIDE CORRECTION. |
| NEC 210.11(C)(1), 210.52(B)(2),(3); FBC RE3703.2 |
| 12. UNIT C DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE |
| LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC |
| 210.52(F); FBC RE3901.8 |
| 13. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER |
| SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED |
| SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| IN THAT SPACE. THE PLAN PROVIDED FOR BOTH UNITS DOES |
| NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION. |
| NEC 210.52(C)(1); FBC RE3901.4 |
| 14. UNIT C SHOWS THE KITCHEN LIGHT ON CIRCUIT B-1. IS |
| THIS LIGHT FED FROM B UNIT FOR SOME REASON, OR SHOULD |
| THIS BE CORRECTED TO BE FED FORM UNIT C? CLARIFY AND/OR |
| CORRECT. FBC 107.2.1 |
| 15. BOTH UNITS SHOW THE DISHWASHER AND DISPOSAL ON ONE |
| CIRCUIT. TYPICALLY, THESE ARE ON SEPARATE CIRCUITS DUE |
| TO THE DEMAND LOAD. IF THE INTENTION IS TO HAVE BOTH OF |
| THESE ON ONE CIRCUIT, PROVIDE SPEC SHEETS OF UNITS |
| SHOWING THE AMPERAGE DRAW TO CONFIRM THE CIRCUIT WILL |
| NOT BE OVERLOADED. NEC 110.3, 215.2, 210.23; FBC |
| RE3701.2 |
| 16. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |