2017-07-18 10:36:51CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLAN SHOWS 2 SERVICES, WHICH IS NOT PERMITTED PER
 CODE. REVISE TO SHOW ONE SERVICE WITH 2 METERS. PROVIDE
 NEW RISER DIAGRAM TO MATCH. PROVIDE LOAD CALCULATION
 FOR ENTIRE SERVICE, PROVIDE ADEQUATE SIZE CONDUCTOR IN
 SERVICE RISER TO ACCOMMODATE LOAD, AND PROPERLY SIZED
 GROUNDING ELECTRODE SYSTEM. NEC 230.2, 215.5, 220,
 250.50; FBC RE3601.2, 3602.1, 3608.1
 2. LOAD CALCULATION PROVIDED FOR EACH UNIT DOES NOT
 INCLUDE THE RANGE. PROVIDE CORRECTION TO INCLUDE THE
 RANGE. NEC 210.19(3), 220.55; FBC RE3602.2, 3702.9.1
 3. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE
 "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING
 IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE
 REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF
 THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 406.12; FBC RE4002.14
 3. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE
 AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE
 ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT
 DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS
 REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE
 CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12
 4. UNIT B SHOW THE BATHROOM OUTLETS ON A 15 AMP
 CIRCUIT, AND IT DOES NOT SHOW A GFCI OUTLET LOCATED
 WITHIN 3 FEET OF THE BASIN. PROVIDE 20 AMP CIRCUIT AND
 OUTLET PER CODE. NEC 210.11(C)(3) , 210.52(D) FBC
 RE3703.4, 3901.6
 5. UNIT B, CIRCUIT 19,21 SHOWS THE AHU ON A 45 AMP
 BREAKER. SPECS FROM MECHANICAL DRAWING SHOW A MAX 30
 AMP BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 6. UNIT B, CIRCUIT 16,18 SHOW A 20 AMP CIRCUIT TO THE
 RANGE. A MINIMUM 40 AMP CIRCUIT IS REQUIRED. PROVIDE
 CORRECTION. NEC 210.19(3), 220.55; FBC RE3602.2,
 3702.9.1
 7. UNIT B SHOWS THE DINING ROOM LIGHT ON THE SAME
 CIRCUIT AS THE DINING ROOM OUTLETS, WHICH IS NOT
 PERMITTED PER CODE. PROVIDE CORRECTION. NEC
 210.11(C)(1), 210.52(B)(2); FBC RE3703.2
 8. UNIT B AND C SHOW ONLY ONE SMALL APPLIANCE CIRCUIT
 FEEDING THE KITCHEN COUNTER OUTLETS. CODE REQUIRES A
 MINIMUM OF 2 CIRCUITS. PROVIDE CORRECTION. NEC
 210.11(C)(1), 210.52(B)(3); FBC RE3703.2
 9. UNIT C, CIRCUIT 18, SHOWS THE BATHROOM OUTLETS ON A
 15 AMP CIRCUIT, WHICH IS NOT PERMITTED PER CODE.
 PROVIDE CORRECTION. NEC 210.11(C)(3); FBC RE3703.4,
 3901.6
 10. UNIT C, CIRCUIT 17,19 SHOWS THE AHU ON A 45 AMP
 BREAKER. SPECS FROM MECHANICAL DRAWING SHOW A MAX 30
 AMP BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 11. UNIT C SHOWS THE DINING ROOM ON A 15 AMP CIRCUIT,
 WHICH IS NOT PERMITTED PER CODE. PROVIDE CORRECTION.
 NEC 210.11(C)(1), 210.52(B)(2),(3); FBC RE3703.2
 12. UNIT C DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE3901.8
 13. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED FOR BOTH UNITS DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE3901.4
 14. UNIT C SHOWS THE KITCHEN LIGHT ON CIRCUIT B-1. IS
 THIS LIGHT FED FROM B UNIT FOR SOME REASON, OR SHOULD
 THIS BE CORRECTED TO BE FED FORM UNIT C? CLARIFY AND/OR
 CORRECT. FBC 107.2.1
 15. BOTH UNITS SHOW THE DISHWASHER AND DISPOSAL ON ONE
 CIRCUIT. TYPICALLY, THESE ARE ON SEPARATE CIRCUITS DUE
 TO THE DEMAND LOAD. IF THE INTENTION IS TO HAVE BOTH OF
 THESE ON ONE CIRCUIT, PROVIDE SPEC SHEETS OF UNITS
 SHOWING THE AMPERAGE DRAW TO CONFIRM THE CIRCUIT WILL
 NOT BE OVERLOADED. NEC 110.3, 215.2, 210.23; FBC
 RE3701.2
 16. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER