Plan Review Notes For Permit 17061318 |
Permit Number |
17061318 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-06 09:17:12 | PLAN DENIED | | 1) PROVIDE DUCT SIZE ON ALL DUCT WORK SUPPLY | | AND RETURN. PER SECTION 107 FBC | | 2) PROVIDE LOCATION AND SIZE OF RETURN AIR | | GRILL ON PLAN. SECTION 107 FBC | | 3) REFER TO SECTION M1401.3 SIZING | | ENERGY CALCULATION REQUIRED WITH PLAN | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|