Plan Review Notes
Plan Review Notes For Permit 17061318
Permit Number 17061318
Review Stop M
Sequence Number 1
Notes
Date Text
2017-08-06 09:17:12PLAN DENIED
 1) PROVIDE DUCT SIZE ON ALL DUCT WORK SUPPLY
 AND RETURN. PER SECTION 107 FBC
 2) PROVIDE LOCATION AND SIZE OF RETURN AIR
 GRILL ON PLAN. SECTION 107 FBC
 3) REFER TO SECTION M1401.3 SIZING
 ENERGY CALCULATION REQUIRED WITH PLAN
  
 PLAN REVIEW BY HAROLD MOSER