Plan Review Notes
Plan Review Notes For Permit 17061318
Permit Number 17061318
Review Stop G
Sequence Number 1
Notes
Date Text
2017-07-18 14:29:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. SHOW LOCATION OF TANKLESS WATER HEATER ON ELEVATION
 PLAN SHT. IN COMPLIANCE OF MANUFACTURE INSTALLATION
 GUIDE 4FT FROM OPERABLE WINDOW. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  