2017-07-19 13:43:52CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. LOAD CALCULATION PROVIDED DOES NOT INCLUDE THE
 RANGE. PROVIDE CORRECTION TO INCLUDE THE RANGE. NEC
 210.19(3), 220.55; FBC RE3602.2, 3702.9.1
 2. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE
 "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING
 IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE
 REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF
 THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 406.12; FBC RE4002.14
 3. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE
 AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE
 ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT
 DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS
 REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE
 CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12
 4. CIRCUIT 25,27 SHOWS THE AHU ON A 25 AMP BREAKER.
 SPECS FROM MECHANICAL DRAWING SHOW A MAX 40 AMP
 BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 5. CIRCUIT 26,28 SHOWS THE CU ON A 45 AMP BREAKER.
 SPECS FROM MECHANICAL DRAWING SHOW A MAX 30 AMP
 BREAKER. PROVIDE CORRECTION. NEC 440.22(C); FBC
 RE3702.11
 6. CIRCUIT 4 SHOW A 15 AMP CIRCUIT TO THE
 RANGE/COOKTOP. A MINIMUM 40 AMP CIRCUIT IS REQUIRED.
 PROVIDE CORRECTION. NEC 210.19(3), 220.55; FBC
 RE3602.2, 3702.9.1
 7. CIRCUIT 15 SHOWS THE DINING ROOM ON A 15 AMP
 CIRCUIT, WHICH IS NOT PERMITTED PER CODE. THE LIGHT IN
 DINING ROOM SHOULD NOT BE ON THE SAME CIRCUIT AS THE
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B)(2),(3); FBC RE3703.2
 8. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. THE ONLY OUTLET SHOWN IS FOR THE
 TANKLESS WATER HEATER (CIRCUIT A-11), AND ALSO IS
 CONNECTED TO BATH #2 GFCI OUTLET. BATH GFCI OUTLETS ARE
 REQUIRED TO BE A 20 AMP CIRCUIT, AND NO OTHER ITEMS CAN
 BE ON THE SAME CIRCUIT, UNLESS THE CIRCUIT REMAINS IN
 ONE BATHROOM ONLY. PROVIDE CORRECTION. NEC 210.63,
 210.11(C)(3), 210.52(D); FBC RE3901.12, 3703.4
 9. CIRCUIT A-22 TO BATH 1 GFCI OUTLET NEEDS TO BE A 20
 AMP CIRCUIT. PROVIDE CORRECTION. NEC 210.11(C)(3); FBC
 3703.4
 10. MASTER BEDROOM DOES NOT COMPLY WITH THE WALL
 SPACING REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
 11. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  