2017-07-05 09:28:43RE-ROOF REVISION , BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- BASE SHEET MECHANICALLY ATTACHED FASTENERS NEED THE
 WITHDRAWAL RESISTANCE TEST (TAS 105) AS REQUIRED BY
 NOTE #10 OF FLORIDA PRODUCT APPROVAL FL2533-R17
 SUBMITTED. PROVIDE 2 SIGNED AND SEALED COPIES OF THE
 TEST. SEC. 1609.1 FBC.
  
 2- THE DESIGN PRESSURES FOR SELECTED SYSTEM LWC-33 IS
 -52.5 PSF. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED
 BY NOTE #8 OF FLORIDA PRODUCT APPROVAL SUBMITTED.
 PROVIDE 2 SIGNED AND SEALED CALCULATIONS. NOTE:
 ENGINEER DOING THE CALCULATIONS TO COORDINATE WITH THE
 TAS 105 RESULTS AS REQUIRED ON ITEM #1 ABOVE.
 SEC. 1609.1 FBC
  